13.2 Troubleshooting table for general errors
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
General errors
Indication
Cause
Measure
Remark
Gas smell
Gas leak
Warning
Close the main gas valve at once.
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.
Warning
Immediately contact your installation engineer or local gas
company.
The display is off
The water heater is off Start the water heater (9 "Starting the water heater")
No supply voltage
present
1. Check whether the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the controller is ON
(position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 V
AC
(-15%, +10%)
See the electrical diagram (17 "Appendices").
If the error persists, consult your installation engineer.
Defective fuse(s)
Replace fuse(s)
To replace the fuses, you must contact your installation engineer.
Summary of Contents for Cyclone BFC-28
Page 4: ...E2...
Page 6: ...4 Instruction manual BFC gis...
Page 10: ...Contents 8 Instruction manual BFC...
Page 31: ...Instruction manual BFC 29 is Installation types IMD 0789 R0 C43 C13 C53 B23 C33...
Page 48: ...Conversion to a different gas category 46 Instruction manual BFC 4 is...
Page 58: ...Status of the water heater 56 Instruction manual BFC 8 gis...
Page 62: ...Shutting down 60 Instruction manual BFC 10 gis...
Page 74: ...Service program 72 Instruction manual BFC 12 is...
Page 88: ...Service interval 86 Instruction manual BFC 14 is...
Page 97: ...Instruction manual BFC 95 is...
Page 102: ...Instruction manual BFC 100...