background image

11

D. Know your own qualifications or those of your contractor. The

solvent welding technique of joining PVC, PVC cellular core, ABS or

CPVC pipe is a specialized skill just as any other pipe fitting technique.

E.  Closely supervise the installation and inspect the finished job before

start-up.

F.  Contact the manufacturer, supplier, or competent consulting agency

if you have any questions about the application or installation of

PVC, PVC cellular core, ABS or CPVC pipe.

G. Take the time and effort to do a professional job. Shortcuts will only

cause you problems and delays in start-up. The majority of failures

in these systems are the result of shortcuts and/or improper joining

techniques.

2. SELECTION OF MATERIALS

PRIMER

It is recommended that Tetrahydrofuran (THF) be used to prepare the

surfaces of pipe and fittings for solvent welding. Do not use water, rags,

gasoline or any other substitutes for cleaning PVC cellular core, ABS or

CPVC surfaces. A chemical cleaner such as MEK may be used.

CEMENT

The cement should be a bodied cement of approximately 500 to 1600

centipoise viscosity containing 10-20% (by weight) virgin PVC material

solvated with tetrahydrofuran (THF). Small quantities of dimethyl formamide

(DMF) may be included to act as a retarding agent to extend curing time.

Select the proper cement; Schedule 40 cement should be used for Schedule

40 pipe. Never use all-purpose cements, commercial glues and adhesives

or ABS cement to join PVC or CPVC pipe and fittings.

SAFETY PRECAUTION: PRIMERS AND CEMENTS ARE E X T R E M E L Y

FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR

OPEN FLAME.  ALSO, USE ONLY IN A WELL-VENTILATED AREA.

CONTROLS AND SWITCHES

The BTH-120 and 250 are provided with four pressure switches.  Both the

BTH 150 and 199 are provided with three pressure switches. These

switches are essential to the safe and proper operation of the unit. All

switches are wired in series. The controller is set up to shut the unit down

whenever there is a failure of any of the switches. It is important to

understand the purpose of each switch.

FIGURE 13

BLOWER PROVER SWITCH

(SEE FIGURE 13)

The Blower Prover Switch is provided on the heater to verify that the fan

is operating. It is a positive pressure switch whose electrical contacts are

normally open. When the fan increases the pressure in the burner, the

pressure switch will allow the electrical contacts to close. The pressure

switch is connected to the burner tap by a piece of tygon tubing. This

Table 2.  VENT LENGTH TABLE

4-inch PVC may be used for a MAXIMUM intake of ONE HUNDRED TWENTY

(120) EQUIVALENT FEET and a MAXIMUM exhaust of ONE HUNDRED

TWENTY (120) EQUIVALENT FEET.  The maximum number of 90° elbows

with the 4-inch venting is six (6) on the intake and six (6) on the exhaust.

A 90° elbow is equal to five (5) equivalent feet of pipe.  One (1) 90° elbow

is equal to  two (2) 45° elbows.  Any venting configuration using less than

50 equivalent feet should use 3-inch venting.  See Table 2.

The 3-inch venting terminals (provided) must be used with the 4-inch

venting by adding 4x3 reducing couplings at the venting terminals.  A

reducing coupling is also needed immediately after the condensate elbow

(exhaust) and immediately before the 3-inch blower adapter (intake) if

direct venting is installed.  See Table 2.

IMPORTANT

When multiple units are direct vented through a wall (3-inch or 4-inch

venting), all intake vent terminals should be no lower than the highest

exhaust vent terminal.

NOTE:  This unit can be vented using only PVC (Class 160, ASTM D-2241

Schedule 40, ASTM D-1785 ; or Cellular Core Schedule 40 DWV, ASTM

F-891) , Schedule 40 CPVC (ASTM F-411), or ABS (ASTM D-2661) pipe.

The fittings, other than the TERMINATIONS should be equivalent to PVC-

DWV fittings meeting ASTM D-2665 (Use CPVC fittings, ASTM F-438 for

CPVC pipe and ABS fittings, ASTM D-2661/3311 for ABS pipe. If CPVC or

ABS pipe and fittings are used, then the proper cement must be used for

all joints, including joining the pipe to the Termination  (PVC Material). PVC

Materials should use ASTM D-2564 Grade Cement; CPVC Materials should

use ASTM F-493 Grade Cement and ; ABS Materials should use ASTM

D-2235 Grade Cement.

NOTE:  for Water Heaters in locations with high ambient temperatures

(above 100°F) and/or insufficient dilution air, it is recommended that CPVC

or ABS pipe and fittings (MUST USE SUPPLIED VENT TERMINAL) be used.

 4. It is important that condensate not be allowed to buildup in the exhaust

vent pipe. To prevent this from happening the pipe should be installed

with a slight, 1/8 inch per five feet (5') of pipe maximum downward

slope.

5. The vent system should be supported every five feet (5') of vertical

run and every three feet (3') of horizontal run of vent pipe length.

NOTE:  Stress levels in the pipe and fittings can be significantly increased

by improper installation. If rigid pipe clamps are used to hold the pipe in

place, or if the pipe cannot move freely through a wall penetration, the pipe

may be directly stressed, or high thermal stresses may be formed when

the pipe heats up and expands. Install accordingly to minimize such stresses.

VENT PIPE PREPARATION

1. INITIAL PREPARATION

A.  Make sure the solvent cement you are planning to use is designed

for the specific application you are attempting.

B.  Know the physical and chemical characteristics and limitations of

the PVC, PVC cellular core, ABS or CPVC piping materials that you

are about to use.

C.  Know the reputation of your pipe and cement manufacturer and

their products.

Number of

3" Minimum

3" Maximum 4" Maximum

90° Elbows

Pipe (Feet)

Pipe (Feet)

Pipe (Feet)

ONE (1)

7

45

115

TWO (2)

7

40

110

THREE (3)

7

35

105

FOUR (4)

7

30

100

FIVE (5)

7

---

95

SIX (6)

7

---

90

Summary of Contents for BTH 120 - 250

Page 1: ...any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier cal...

Page 2: ...20 125 000 Nat 60 475 356 285 237 203 178 158 142 129 119 110 102 BTH 120 120 000 L P 60 456 342 274 228 195 171 152 137 124 114 105 98 BTH 150 150 000 Nat 100 570 427 342 285 244 214 190 171 155 142...

Page 3: ...hecking the proper functioning of the heater In addition to these instructions the equipment shall be installed in accordance with those installation regulations in force in the local area where the i...

Page 4: ...r may be able to make minor operational adjustments and save himself unnecessary service calls However the user should not attempt repairs which are not listed in this section WATERTEMPERATURECONTROL...

Page 5: ...personal injury or death Do not apply insulation to the top or the upper 15 of the water heater as this will interfere with safe operation Do not cover the temperature pressure relief valve Do not cov...

Page 6: ...TEDTOTHEOUTDOORS AND HAS ADEQUATE AIR SUPPLY TO AVOID RISKS OF IMPROPER OPERATION FIRE EXPLOSIONORASPHYXIATION VENT PIPE TERMINATION NOTE Before installing venting determine place of vent pipe termina...

Page 7: ...E ON AIR INTAKE TERMINAL DIRECT VENT HORIZONTAL VENT FIGURE 6 DO NOT TERMINATE EXHAUST OVER PUBLIC AREA WHERE CONDENSATE OR VAPOR CAN CAUSE NUISANCE OR HAZARD EXHAUST VENT HOOD MUST BE LOCATED 1 MINIM...

Page 8: ...n the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pipes serving power vented appliances are classified by building codes as vent connectors Required clear...

Page 9: ...the holes by drilling a hole through the center of the template from the inside through to the outside The template can now be positioned on the outside wall using the drilled holes as a centering po...

Page 10: ...ith a plumbing roof boot or equivalent flashing 3 The intake vent termination and the exhaust vent termination must penetrate the same side of roof 4 The center line of the intake vent termination and...

Page 11: ...intake and six 6 on the exhaust A 90 elbow is equal to five 5 equivalent feet of pipe One 1 90 elbow is equal to two 2 45 elbows Any venting configuration using less than 50 equivalent feet should use...

Page 12: ...improvements have been made to strengthen the igniter it is still fragile and care must be taken when handling the igniter to prevent breakage GAS PIPING Contact your local gas service company to ensu...

Page 13: ...rements of all other gas fired equipment supplied by the meter If the gas meter is too small ask the gas company to install a larger meter having adequate capacity GAS PRESSURE REGULATION Main line ga...

Page 14: ...Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNECTIONS This manual provides detailed install...

Page 15: ...the state of other system devices If the temperature drops below the setpoint value less differential the control will automatically return to step 2 and repeat the entire operating cycle During this...

Page 16: ...ate 3 Not Implimented h s 240 Executed State 4 Not Implimented h s 210 Executed State 10 Not Implimented h s 213 Executed State 13 Not Implimented h s 214 Executed State 14 Not Implimented h s 216 Exe...

Page 17: ...ol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring shorted...

Page 18: ...unit is equipped with the correct orifice PRIOR TO START UP REQUIREDABILITY INSTALLATIONORSERVICEOFTHISWATERHEATERREQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUM...

Page 19: ...19 FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Page 20: ...below 160 F HIGH ALTITUDE INSTALLATIONS WARNING BTH HEATERS ARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONS ABOVE 6500 FEET MAY REQUIREREPLACEMENTOFTHEBURNERORIF...

Page 21: ...drain valve when finished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and s...

Page 22: ...operation and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFOREMANUALLYOPERATINGTHEVALVE MAKESURETHATA...

Page 23: ...WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS...

Page 24: ...GER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT AD...

Page 25: ...NIFOLD KIT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONSFORTHERMALEXPANSIONOFWATERINTHEHOTWATER SYSTEM MU...

Page 26: ...RCULATINGLINEOF180 FORBOOSTEDWATER IF USED TOINLETWATERLINETOBOOSTER INSTALLINACCORDANCEWITHLOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULAT...

Page 27: ...INTHETANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BECONNECTEDATPOINTA DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEEWATERTEMPERATURECONTROLWARNINGONPAGE5 IF HIGHER...

Page 28: ...er heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold k...

Page 29: ...leaned Refer to MAINTENANCE for details 2 Some of the electrical components of the water heater make sounds which are normal Contacts click or snap as the heater starts and stops Transformers often hu...

Page 30: ...0 W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 W C for BTH 120 250 or 4 5 W C for BTH 150 199 or for L P Gas 11 0 W C pressure Also the manifold p...

Page 31: ...r the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but are not limited to a Labor cha...

Page 32: ...32 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 WWW HOTWATER COM E MAIL PARTS HOTWATER COM...

Reviews: