5. TECHNICAL PARAMETERS
Voltage, current and power consumption for different heat
recovery units
[number of phases / V / A / W]
Type
Maximum
air flow
[m
3
/h]
Intake
filter class
Exhaust
filter class
Frequen-
cy
[Hz]
HRWA1-...-.S0...
HRWA1-...-.E1...
HRWA1-...-.V1...
Weight*
[kg]
HRWA1-040-E...
400
EPM 1 55%
(F7)
Coarse 60%
(G4)
50
1 / 230 / 9,2 / 1840
1 / 230 / 15,8/ 3340
1 / 230 / 9,2 / 1840
94
HRWA1-040-X...
400
EPM 1 55%
(F7)
Coarse 60%
(G4)
50
1 / 230 / 2,7 / 340
1 / 230 / 9,2 / 1840
1 / 230 / 2,7 / 340
93
HRWA1-070-E...
700
EPM 1 55%
(F7)
Coarse 60%
(G4)
50
1 / 230 / 11,4 / 2340
3 / 400 / 9,8 / 4590
1 / 230 / 11,4 / 2340
128
HRWA1-070-X...
700
EPM 1 55%
(F7)
Coarse 60%
(G4)
50
1 / 230 / 2,7 / 340
1 / 230 /12,5 / 2590
1 / 230 / 2,7 / 340
127
HRWA1-100-E...
1000
EPM 1 55%
(F7)
Coarse 60%
(G4)
50
3 / 400/ 7,5 / 3770
3 / 400 / 11,8 / 6770
3 / 400/ 7,5 / 3770
151
HRWA1-100-X...
1000
EPM 1 55%
(F7)
Coarse 60%
(G4)
50
1 / 230 / 5 / 770
3 / 400 / 9,3 / 3770
1 / 230 / 5 / 770
150
The listed weight is valid for the heaviest unit in a given class
The rest of technical data can be found in the technical catalogue
6. INSTALLATION
Select unit location
It is recommended that a ventilation system should always be designed by a licensed HVAC designer or Engineer.
TECHNICAL INFORMATION
Unit is designed for indoor installation only, with an interior temperature between
+5C and 40C .
+5°C
+40°C
The incoming air must have a temperature ranging from -15°C to +40°C and a relative humidity of up to 90%.
If exterior air coming into the unit is lower than -15C then unit may intitiate anti-frost protection mode to pre-
vent the damage of interior componets due to freezing.
-20 °C
+40 °C
max. 90%
15 °C