Electric power cable
•
The power cable is not included. It has to be procured be-
fore the installation. Choose the type and thickness of the
cable according to the unit’s maximum power consump-
tion and the specific requirements of the place of installa-
tion.
TECHNICAL INFORMATION
•
The electrical parameters can be found on the manufacturer's
labels inside and on the side of the unit
All the unit's electrical circuits must be connected through
an earth leakage breaker according to the current model.
The unit must be connected in a way that it can be discon-
nected from the power supply with one breaker.
Table of minimum breaker sizes according to heat recovery
unit
model.
Recommended minimum circuit breaker values:
-XS0...
-ES0...
-EE1...
-EV1...
-XE1...
-XV1...
HRWA1-040-...
4A (1F)
10A (1F)
16A (1F)
10A (1F)
10A (1F)
4A (1F)
HRWA1-070-...
4A (1F)
13A (1F)
10A (3F)
13A (1F)
13A (1F)
4A (1F)
HRWA1-100-...
6A (1F)
10A (3F)
13A (3F)
10A (3F)
10A (3F)
6A (1F)
Accessories
Connect electrical accessories for the unit to the electronic
terminals as shown in the wiring diagrams located on the
unit.
6. INSTALLATION
The power cord connects directly to the unit‘s main
switch in the control box