6. INSTALLATION
TECHNICAL DATA
All unit models must be installed in an upright position according to the figure below. Any other postion is strictly prohibited
and will invalidate the warranty
The unit must be installed so that the air inlets and outlets correspond with the direction of the air flows in the ventilation
system. The unit must be installed to provide access for maintenance, repairs or disassembly. This includes access to
dampers in order to inspect them, access to the controls box inside unit, and unit panels to access interior of the unit for
filter changes and other components
6.1-2 Safe installation distance
ATTENTION!
•
All materials used within a distance of less than 100 mm from the ventilation unit must be non-flammable (do not burn,
or flare up) or less flammable (do not burn, but decompose – e.g. drywall). These materials must not cover unit inlets
and outlets.
•
The safe distance of flammable materials from the entry neck of the unit is 500 mm.
•
The safe distance of flammable materials in the remaining directions is 100 mm.