9. FAULTS REMOVAL
ATTENTION!
● Before you start a perform maintenance and repair works, the unit must be disconnected from the power source and the
supply voltage locked, service switch in 0 position (off).
● Do not start repairs, if you are not sure of or do not know the exact procedure, and contact the specialized service!!!
TECHNICAL DATA
Defect is usually indicated by message on the display, see the table below.
Description
Unit's behaviour
Likely problem
Solution
1 - Request for filter calib
-
ration
Unit is working
after resetting the unit, or
while recording the control
after inserting new filters enter menu
1616 on line 05 and calibrate the filters
4 – Supply fan error
Unit is not working
Overheated fan or defect on
thermal contact of inlet fan
Determine the cause of the overheating
(defective bearing, short-circuit...) or
replace the engine.
5 – Exhaust fan error
Unit is not working
Overheated fan or defect on
thermal contact of inlet fan
Determine the cause of the overheating
(defective bearing, short-circuit...) or
replace the engine.
6 – Inlet filter clogged
Unit is working
Clogged filter
Check the condition of the filter, or repla
-
ce it. If the unit does not have a pressure
sensor for the filter, RESET the clogged
filter according to the manual.
7 – Exhaust filter clogged
Unit is working
Clogged filter
Check the condition of the filter, or repla
-
ce it. If the unit does not have a pressure
sensor for the filter, RESET the clogged
filter according to the manual.
8 - Failure in preheating 1
Unit is working
Overheated electric ex
-
changer or damaged sen
-
sor Open the exchanger
thermostat.
Check that air can flow freely through
the unit, electric heat exchanger is not
cooling sufficiently. Check the safety
thermostat on the electric preheating for
damages.
9 - Failure in exchanger 1
Unit is working
Overheated electric ex
-
changer or damaged sen
-
sor Open the exchanger
thermostat.
Check that air can flow freely through
the unit, electric heat exchanger is not
cooling sufficiently. Check the safety
thermostat on the electric reheating for
damages.
10 - Failure in exchanger 2
Unit is working
Overheated electric ex
-
changer or damaged sen
-
sor Open the exchanger
thermostat.
Check that air can flow freely through
the unit, electric heat exchanger is not
cooling sufficiently. Check the safety
thermostat on the electric reheating for
damages.
11 - Failure in preheating 1
Unit is working
Overheated electric ex
-
changer or damaged sen
-
sor Open the exchanger
thermostat.
Check that air can flow freely through
the unit, electric heat exchanger is not
cooling sufficiently. Check the safety
thermostat on the electric preheating for
damages.
12 – CO2 sensor failure
Unit is working
Defective air quality sensor
Check that the CO2 sensor is connec
-
ted correctly or check that it is operating
correctly (output signal value)
13 - Failure of rotary heat
exchanger
Unit is not working
Failure of rotary heat ex
-
changer
Check that the input error is correctly
connected to the electronics or check
what type of error the heat exchanger is
indicating.