2N TELEKOMUNIKACE a.s., www.2n.cz
26/92
Requirements
Keep the LED polarity (see the cover print).
Keep the colours: request confirmation – yellow, connection confirmation –
green.
Note
The printed circuit LED is off in this type of connection.
CANCEL Connection (Door Contact, Optional)
Caution
Make sure that the door switch or door opening signal indicates that the
door is open only if both the internal and external lift doors are open and
the people can leave the cabin.
Note
Using the CANCEL input, program parameter 914 to a time value longer
than the maximum lift travel time (i.e. the closed door time). If
parameter 914 is set to 0, the CANCEL connection is meaningless and
thus needless.
Switch control
Connect the switch to the CANCEL terminal.