Installation of the Oil Tector Remote Alarm Continued
6. Connect the Oil Tector Remote Alarm to the auxiliary contacts
marked C, O & W in the control panel. C on the alarm to C in the panel.
O on the alarm to O in the panel. W on the alarm to W in the panel.
Use 18 awg, 3 conductor cable. CAUTION: The auxiliary cotacts are
low voltage wires and cannot be run in a conduit with High voltage
wires.
6. Plug in the power supply into a 120VAC, 50/60 HZ
standard wall outlet. The green “Normal” light should
come on.
5 ft max
7. Test the system by pressing the “Alarm Test” button. The
buzzer, the red “High Water” light & the red “High Oil” light will be
“on”. Release the “Alarm Test” button and the alarm buzzer and
indicator lights will automatically reset. Test product weekly to
ensure system integrity.
Alarm
Connects To
Auxiliary Contacts On
Circuit Board In Panel