81 / 138
Identification: MD-AL-GI-00
Rev. 1.1 of 15/03/2021 - Application: GID
User’s Manual 3PH 50000TL-60000TL-V1
Rev. 1.1 15/03/2021
Technical Support.
ID94
The software version is
unsuitable
The software between
the control board and
communication board
is unsuitable.
Contact Technical Support to update
the software.
ID95
Faulty EEPROM
communication board.
The EEPROM of the
communication board
is faulty.
ID95-ID96 are internal faults of the
inverter; turn off the “DC switch”, wait
5 minutes and then turn it back on
again. Check that the fault is no longer
present. If this is not the case, contact
Technical Support.
ID96
Faulty RTC clock chip
The RTC clock chip is
faulty.
ID97
Invalid country code
The country code is
not valid.
Check the configuration of the
country, as indicated in relative
section (C) “5. Country” of this user
manual; if it is not correct, change it
according to relative section (A) “4.
Configuration of country code” of this
manual.
ID98
MicroSD card fault
The microSD card is
faulty or a false
contact has occurred.
Replace the SD card.
ID99-
ID100
Reserved
Reserved
Reserved
7.2.
Maintenance
Inverters generally do not require daily or routine maintenance. In any case, for proper long-term operation
of the inverter, make sure that the heatsink for cooling the inverter has enough space to ensure adequate
ventilation and that it is not obstructed by dust or other items.
Cleaning the inverter
Use an air compressor, a soft dry cloth or soft-bristled brush to clean the inverter. Do not use water, corrosive
chemical substances or aggressive detergents to clean the inverter. Disconnect the AC and DC power to the
inverter before performing any cleaning operations.
Cleaning the heatsink
Use an air compressor, a soft dry cloth or soft-bristled brush to clean the heatsink. Do not use water,
corrosive chemical substances or aggressive detergents to clean the heatsink. Disconnect the AC and DC
power to the inverter before performing any cleaning operations.