113 / 138
Identification: MD-AL-GI-00
Rev. 1.1 of 15/03/2021 - Application: GID
User’s Manual 3PH 50000TL-60000TL-V1
Rev. 1.1 15/03/2021
Figure 74 - Final status of LEDs
Status of LEDs present on the adapter
1)
Irregular communication with inverter
-
NET (left LED): on
-
COM (central LED ): off
-
SER (right LED): on
Figure 75 - Irregular communication status between inverter and adapter
-
Check the Modbus address set on the inverter:
Enter the main menu with the ESC key (first key on the left), go to System Info and press
ENTER to enter the submenu. Scroll down to the Modbus address parameter and make sure it
is set to 01 (and in any case, other than 00).
If the value is not 01, go to “Settings” (basic settings for hybrid inverters) and enter the
Modbus Address menu where the 01 value can be set.