13
Note:
Error – a condition that affects the electronics, actuator reacts according to “
Response to failure and SAFE
signal“ (SAFE – external signal, which can impose error condition to the actuator. May use, for instance, when
the actuator must be set as an error because the error occurred in another device).
Warning – condition, which is only indicated, will not affect the electronics.
Can be set what condition will be evaluated as a
Warning and what as an Error.
Procedure of setting parameters by means of push-buttons
For simple programming of required operating parameters, the control unit is fitted with four push-buttons:
MENU, P, O, C and three signal lamps.
-
-
-
System without feeding
-
-
lit on
Everything OK – working regime
(remote, local or switched off control)
-
blinking
lit on
Error or warning – working regime
(remote, local or switched off control)
lit on
-
lit on
Enter or exit of Setting of parameters by means of push-buttons
or Setting of parameters by means of PC
blinking
-
lit on
blinking blinking
lit on
Setting of parameters by means of push-buttons
blinking
lit on
lit on
Zápis poloha zavřeno, otevřeno a autokalibrace
– The actuator is set to position Closed and position Closed is stored by long pressing of push-button
C –
until the
LED1 turns on
(without entering the Menu).
– The actuator is set to position Open and position Open is stored by long pressing of push-button
O –
until the LED1
turns on.
– The calibration routine is started by means of push-button
P
(in remote control)
that, in the three-position regulation,
will measure actual inertial masses of the system and store them into the memory of the control unit.
This function is designed for 3P regulation only and serves to measure the inertial mass.
– In case the actuator stroke is to be increased and the switching off is set to
“from position“, the actuator will
switch off during shifting in position 0 or 100 %. To further change the position, press
C or O, and, while keeping it
depressed, the actuator can be further shifted.
Overview of MENU
BROWSING THROUGH MENU
– The setting mode is entered by pressing and keeping depressed push-button
MENU for at least 2 s; LED1 is then lit on.
– Shortly press
MENU to select the basic MENU – menu M1 to M8
(LED1 signalizes the menu number);
by short pressing
of
P, O, C they are entered
(LED2 signalizes particular parameter).
– Shortly press
P to select required value of the parameter. In case the parameter can be set to several values, they are
changed by short pressing of P
(number of blinking of LED2 indicates its value).
Keep pressing of P to record the
chosen parameter; the record is confirmed by lighting on of LED2.
– Shortly press
MENU to gradually set the required menu and parameters.
– After setting all required parameters, exit the setting menu by pressing and keeping depressed push-button
MENU for at
least 2 s. The setting menu will also be left in case that no push-button is pressed within 1 minute.
COM
POWER
TORK
AIN
LED1 LED2 LED3
MENU
P
O
C
Push-buttons and signal lamps LED on control unit DMS2.ED.S and DMS2.ED.S90
Colours of diodes:
LED1 – yellow
(menu number)
LED2 – red
(parameter value)
LED3 – green
Yellow
Red
Green
State
Содержание MODACT MOKPED 100 Ex