– In version DMS2ED with display is shown number of the current error in the display.
– Errors / warnings EEPROM, RAM, ROM, Reset are internal electronics errors
– for EEPROM warning restore parameters from a backup, unless you have not saved the last state as a backup, if so
check and reset of some parameters is necessary.
Restoring parameters from backup – can be done from PC or by using buttons on the sensor:
– turn off power of electronics
– press and hold O + C buttons
– turn the power on
(all LED lit)
– wait for blink of yellow and red LED, by this writing of back up parameters is signalled
– RAM error is in operation corrected automatically by reloading parameters from EEPROM to RAM
– ROM error signals overwrite of program memory, this sensor must be replaced
Terminal board of the actuator with DMS2 ED electronics
If the actuator is of the single-phase version the power supply is connected only to terminals
PE, N, U. The
terminals
V, W remain non-connected. If the actuator is of the version
“Replacement of electric-mechanical board”
with three-phase electric motor without power relays, the electric motor is connected to a separate terminal board
(not shown here).