ZPA Pecky, a.s. 52 442 Скачать руководство пользователя страница 8

8

The actuators with regulator ZP2RE5 are fitted with simpler controlled brakes 

BR2. They are interconnected  

with the regulator that provides impulse for action. 

According to the electric motor output, corresponding variant is chosen:  

BR2 550  of output up to 550 W,

 

BR 2.2 

of output up to 2.2 kW.

If outputs higher than 2.2 kW are to be braked, electric motors of special version with an electromagnetic brake 

should be used.

Switching of electric motor, contactor unit

The actuators in variants Control are fitted with built-in reversing contactor combinations. These are assembled 

of two contactors and an over-current relay. The combination also includes mechanical blocking that prevents both 
contactors  from  being  closed  at  the  same  time. This  could,  for  instance,  happen  in  case  of  wrong  connection  of 
jumpers on the terminal board. The blocking is not dimensioned for long-term action. The over-current relays protects 
the electric motor against over-loading and is dimensioned with respect to its output. 

According  to  the  actuator  version,  the  contactors  are  controlled  by  the  regulator,  change-over  switch  of  local 

control or external input. Control voltage is 230 V / 50 Hz as a standard; it is supplied via contacts of position and/or 
moment micro-switches. Thus, these micro-switches need not be led out of the actuator.

The contactors used have a long mechanical service life and great reserve in switching ability; consequently, the electric 

service life is also sufficient for particular use. The thermal relay is chosen so that it would reliably protect the electric motor 
against overload. Set-up and outfit of the actuators provide for simple connection to power-supply and control circuits. 

The power-supply circuits can be common for the whole group of actuators, which will save the cabling.

6. ELECTRIC PARAMETERS  

External electric connection 

a)  Terminal board

The electric actuator is equipped with a terminal board for connection to external circuits. This terminal board uses 

screw terminals allowing conductors with a maximum cross-section 4 mm

2

 to be connected. Access to the terminal 

board is obtained after removal of the terminal box cover. All control circuits of the electric actuator are brought out to 
the terminal board. The terminal box is fitted with cable bushings for connecting the electric actuator. The electric motor 
is fitted with an independent box with a terminal board and a bushing. 

b)  Connector 

According to the customer's requirements the 

MODACT MTN, MTP actuators can be fitted with the connector to 

provide for connection of control circuits. This connector uses screw terminals allowing conductors with a maximum 
cross-section 4 mm

2

 to be connected. ZPA Pečky, a.s. also supplies a counterpart for the cable. In order to connect the 

cable to this counterpart it is necessary to use special crimping pliers.

Actuator internal wiring

The  internal  wiring  diagrams  of  the 

MODACT  MTN,  MTP  actuators  with  terminal  designation  are  shown  in this 

Mounting and operating instructions.

Each  actuator  is  provided  with  its  internal  wiring  diagram  on  the  inner  side  of  the  terminal  box. The  terminals  

are marked on a self-adhesive label attached to a carrying strip under the terminal block.

Current rating and maximum voltage of microswitches

Maximum voltage of mikroswitches is 250 V AC as well as DC, at these maximum levels of currents.
MO, MZ 

 

250 V AC / 2 A; 250 V DC / 0,2 A

SO, SZ 

 

250 V AC / 2 A; 250 V DC / 0,2 A

PO, PZ  

 

250 V AC / 2 A; 250 V DC / 0,2 A

The microswitches can only be used as single-circuit devices. Two voltages of different values and phases cannot 

be connected to the terminals of the same microswitch.

Isolation resistance

Isolation resistance of electric control circuits against the frame and against each other is min. 20 M

Ω

. After a dump 

test,  isolation  resistance  of  control  circuits  is  min.  2  M

Ω

.  Isolation  resistance  of  the  electric  motor  is  min.  1.9  M

Ω

See Technical specifications for more details.

Electric strength of electric circuits isolation

Circuit of the resistance transmitter   

   500 V, 50 Hz

Circuit of the current transmitter  

     50 V DC

Circuits of microswitches and anti-condensation heater  1,500 V, 50 Hz
Electric motor  

Un = 3 x 230/400 V 

1 800 V, 50 Hz

Содержание 52 442

Страница 1: ...Type numbers 52 442 52 443 Electric Linear Pull rod actuators 4 19 MOUNTING INSTRUCTIONS...

Страница 2: ...ZPA Pe ky a s is certified company in accordance with ISO 9001 as amended...

Страница 3: ...tion or in the tropical atmosphere the anti condensation heater which has been built in all actuators should be always used One or two heater elements should be connected as required Installation of t...

Страница 4: ...tervals The load factor N N R shall be maximum 25 per cent the longest operation cycle N R is 10 minutes The maximum number of switching actions in automatic control mode is 1200 actions per hour The...

Страница 5: ...trol IP 67 Noise Acoustic pressure level A max 85 dB A Acoustic power level A max 95 dB A Tripping thrust At the factory the tripping thrust has been adjusted within the min max range giving in Table...

Страница 6: ...lling switch and the SZ CLOSE signalling switch are used Each of these switches acts only in one direction of output shaft rotation The operating point of the microswitches can be set within the whole...

Страница 7: ...our pole The change over switches are installed in a terminal board box and the control elements on the lid of this terminal board box Position regulator The position regulator built in in the actuato...

Страница 8: ...rminals allowing conductors with a maximum cross section 4 mm2 to be connected Access to the terminal board is obtained after removal of the terminal box cover All control circuits of the electric act...

Страница 9: ...e three phase asynchronous motor 1 drives via countershaft gearing 2 the sun gear of a differential gear unit enclosed in the supporting actuator box power gear transmission 3 In the mechanical power...

Страница 10: ...the transmitter support is positioned at an angle of 180 C with respect to the illustrated position Fig 2a Base plate design with current transmitter 14 66 13 17 67 15 66 16 75 66 12 Legend 12 Torque...

Страница 11: ...direction whereas the segment 24 is designed for the OPEN direction The torque control unit is also fitted with a locking mechanism On operation of the torque limiting switch thismechanism locks this...

Страница 12: ...ranges of adjustment of the signalling switches and the transmitter are required to be changed the position of adjusting wheel K3 should be changed For this purpose the signalling unit should be parti...

Страница 13: ...wheel 62 This wheel is rotated step by step by gear wheels driving cam 57 60 Turning of the cam up to the lever of the CLOSE or OPEN position limit switch PZ or PO causes the switches to change over H...

Страница 14: ...ter 1 x 100 This transmitter has one sided shaft and at its end is fixed a twin wheel 73 composed of gears A and B The principle of drive and transmitter adjustment is equal as at current transmitter...

Страница 15: ...rise up to the resistance value corresponding to the end position open 50 ohms until max 98 ohms Transmitter is set up by this way e Current position transmitters At the first is necessary to set up s...

Страница 16: ...ssary to increase the feeding voltage within the range of recommend values or to decrease total resistance of the current loop R Caution The transmitter CPT 1Az must not be connected without checking...

Страница 17: ...se Press the push button 4 then the push button 20 and keep them depressed until LED blinks When the sense of rotation is changed the end limit positions 4 mA and 20 mA remain valid but the working ra...

Страница 18: ...the actuator is to be stored for a longer period than 3 years then prior to commissioning oil refilling should be made Any manipulation of the equipment at a temperature below 25 C is forbidden Storin...

Страница 19: ...ng to Point 3b Caution The control box cover should be removed so that it is displaced in the direction of extended axis of the actuator output shaft taking care to avoid any damage to the position in...

Страница 20: ...gap that has been thereby disclosed This procedure should be made with the pull rod in the CLOSED position 13 FAILURES AND THEIR REMOVAL Actuator in the end position does not start with motor droning...

Страница 21: ...43 Figs 4 5 6 Type No 52 443 Figs 7 Position transmitter block of local control MODACT MTN MTP actuators 9th place of t no current transmitter 4 20 mA current transmitter 4 20 mA with BMO without BMO...

Страница 22: ...of columns B 150 mm Character on 7th place Ba1I Ba1II Ba1III Ba2I Ba2II Ba2III Bb1I Bb1II Bb1III Bb2I Bb2II Bb2III Bg2I C D E F G H I J K L M P R Spacing of columns Position Closed Thread of coupling...

Страница 23: ...f b ch g e a f b ch g e a 40 a b g a b g max 38 253 max 595 261 max 334 153 100 25 c a d b h g d b h g c a Design 1 M 20 M 20 297 26 A B A B Design 2 Detail of coupling M 20 x 1 5 I M 16 x 1 5 II M 10...

Страница 24: ...g 130 c a 308 d b 352 h g 408 e a 633 f b 677 ch g 733 max 595 max 334 261 325 e a c a d b h g 253 100 153 a b g M20 26 f b ch g 25 215 99 90 e a c a d b h g f b ch g a b g 40 M20 A B Design 1 Detail...

Страница 25: ...ype No 52 443 x1xxx Fig 5 697 436 M30x2 M30 160 261 350 257 835 36 48 60 120 485 376 120 200 with block of terminals with connector External protectivet erminal Local control 697 436 M30x2 M30 160 261...

Страница 26: ...on unit for MODACT MTN MTP 40 electric actuators Type No 52 443 x2xxx design with flange non standard other dimensions and designs of actuators are according to fig 14 15 16 215 160 4x 13 80H8 105 0 2...

Страница 27: ...Q1 MO OPEN torque limit switch SQ2 MZ CLOSE torque limit switch SQ3 PO OPEN position limit switch SQ5 PZ CLOSE position limit switch SQ4 SO OPEN signalling switch SQ6 SZ CLOSE signalling switch SA1 LO...

Страница 28: ...ervomotor MODACT MON MOP Control se styka i a BMO se svorkovnic Wiring diagram of MODACT MTN MTP Control electric actuators with contactors with terminal board P3 0947 Outlet position Control phase BA...

Страница 29: ...servomotor MODACT MON MOP Control se styka i a regul torem ZP2 RE5 se svorkovnic Zapojen elektrick ch servomotor MODACT MON MOP Control se styka i regul torem ZP2 RE5 a BM se svorkovnic with terminal...

Страница 30: ...jumper into clamps t1 t2 Control signal 0 4 20 mA Outlet Position 3 phase motor Brake BR2 blue blue brown brown BRAKE Connect surge voltage protectors to contactor coils O C L R Zapojen elektrick ch s...

Страница 31: ...orem Zapojen elektrick ch servomotor MODACT MON MOP Control se styka i a BMO s konektorem P3 0953 P3M 0954 SA2 O C SA1 L R Wiring diagram of MODACT MTN MTP Control electric actuators with contactors O...

Страница 32: ...iagram of MODACT MTN MTP Control electric actuators with contactors and ZP2 RE5 regulator Wiring diagram of MODACT MTN MTP Control electric actuators with contactors ZP2 RE5 regulator and BMO with con...

Страница 33: ...the control box Sealing ring 60x50 PN 02 9280 2 1 Sealing of output shaft in the control box cover Sealing ring 190x3 PN 02 9281 0 Sealing of control box cover Potentiometer 2 x 100 2340510232 1 Moun...

Страница 34: ...34 NOTES...

Страница 35: ...ary multi turn actuators MODACT MO EEx MOED EEx Explosion proof electric multi turn actuators MODACT MOA Electric multi turn actuators for nuclear power stations application outside containment MODACT...

Страница 36: ...tel 420 321 785 141 9 fax 420 321 785 165 420 321 785 167 e mail zpa zpa pecky cz ZPA Pe ky a s t 5 kv tna 166 289 11 PE KY Czech Republic www zpa pecky cz...

Отзывы: