ZPA Pecky, a.s. 52 442 Скачать руководство пользователя страница 12

12

the minimum and maximum torques. In this way, the amount of tripping torque 

(in Nm)

 per scale division is obtained, 

making it possible to determine by interpolation the scale division with which the slot in the segment 27 or 28 should 
tally. The colour division line which is the nearest to number 10 marks the point of adjustment of the maximum tripping 
torque, whereas the other division line shows the point of adjustment of the minimum tripping torque. The torque control 
unit should be never adjusted so that the slot in the lower segment is outside the zone marked by the colour scale 
division lines. After adjustment of the tripping torque, retighten the lock screw 25 or 26 and the lock nut 44.

b)  Signalling unit (Fig. 4) 

This unit transmits an electrical signal to indicate the position of the output shaft of the actuator, drive of the unit being 

provided via gear wheel 38 by the output shaft through a multistage gearbox to the cams 30 and 31 which control the OPEN 
signalling microswitch 36 

(SO)

 and the CLOSE signalling microswitch 37 

(SZ).

 The instant of operation of the signalling 

switches can be selected at any point of the working stroke of the actuator except the narrow band about the end positions. 

(The signalling switch should close before the position-limit switch while the output shaft is still moving).

 The upper cam 37 

operates in the CLOSE direction, whilst the lower cam 36 operates in the OPEN direction. 

 

Designed as an independent assembly unit, the signalling unit has been assembled on the support 39 under which there are 
gears arranged as shown in the kinematic diagram of the Fig. 5. This gearing has been assembled so that the adjusting 
wheel K3 can be moved to different levels designated I, II and III after loosening of the lock screw 47. In this way, the range of 
adjustment  of  the  signalling  switches  and  the  position  transmitter  can  be  changed,  depending  on  the  working  stroke  of  
the actuator. Fig.5 is a table showing the ranges of adjustment for the individual positions of the adjusting wheel K3.

Adjustment of the signalling unit

If  the  ranges  of  adjustment  of  the  signalling  switches  and  the  transmitter  are  required  to  be  changed  the 

position  of  adjusting  wheel  K3  should  be  changed.  For  this  purpose,  the  signalling  unit  should  be  partially 
withdrawn from the control box 

(which is possible due to a sufficient length of lead-in wires of the microswitches). 

This can be done after removal of the 3 screws 66 

(Figs 2 and 2a)

 used for mounting the unit onto the base 

plate. After the signalling unit has been adjusted to the required range it should be brought back into its original 
position. Before retightening the screws 66, the correct meshing of gears K1 and K2 should be checked 

(see 

Fig. 5).

 Put on at the lower end of the camshaft 48 

(Fig. 5)

 is the pinion 49 

(Fig. 5)

 which is connected to the 

shaft 46 by an adjustable friction clutch. On this pinion, the motion required for driving the potentiometer position 
transmitter  is  sensed. The  arrangement  of  cams  and  microswitches  of  the  signalling  unit  is  shown  in  Fig.  4. 
Shoulders of the cams 30 or 31 deflect the levers 34 and 35, which in turn control the microswitches 36 

(SO)

 

and 37 

(SZ)

. When adjusting the signalling and position-limit switches and the position transmitter, the output 

shaft of the actuator should be moved to the position in which changing-over of the microswitches should take 
place or the required position of the position transmitter cursor should be reached. When adjusting the signalling 
switches, the following procedure should be used: First, loosen the screws 32 

(for the CLOSE signalling switch 

SZ)

 or 33 

(for the OPEN signalling switch SO),

 as shown in Fig. 4. Then, turn the cam 30 or 31 in the direction 

of the arrowhead till the microswitch closes. In this position, hold the cams and retighten the lock screws.

Diagram of microswitches

Fig. 4 -

 

Signalling unit

30 

    33 

          35

  31 

  32 

     34 

       36 

         37           38             39

Legend:

30 –  CLOSE direction cams
31 –  OPEN direction cams
32 –  Screws of CLOSE direction cams
33 –  Screws of OPEN direction cams
34 –  OPEN direction lever
35 –  CLOSE direction lever
36 –  OPEN direction microswitch (lower)
37 –  CLOSE direction microswitch (upper) 
38 –  Drive gear
39 – Supporting plate of signalling unit

The encircled numbers correspond to the numbers of termi-
nals on the terminal board of the actuator.
The microswitches can be used as one–circuit devices only.

Содержание 52 442

Страница 1: ...Type numbers 52 442 52 443 Electric Linear Pull rod actuators 4 19 MOUNTING INSTRUCTIONS...

Страница 2: ...ZPA Pe ky a s is certified company in accordance with ISO 9001 as amended...

Страница 3: ...tion or in the tropical atmosphere the anti condensation heater which has been built in all actuators should be always used One or two heater elements should be connected as required Installation of t...

Страница 4: ...tervals The load factor N N R shall be maximum 25 per cent the longest operation cycle N R is 10 minutes The maximum number of switching actions in automatic control mode is 1200 actions per hour The...

Страница 5: ...trol IP 67 Noise Acoustic pressure level A max 85 dB A Acoustic power level A max 95 dB A Tripping thrust At the factory the tripping thrust has been adjusted within the min max range giving in Table...

Страница 6: ...lling switch and the SZ CLOSE signalling switch are used Each of these switches acts only in one direction of output shaft rotation The operating point of the microswitches can be set within the whole...

Страница 7: ...our pole The change over switches are installed in a terminal board box and the control elements on the lid of this terminal board box Position regulator The position regulator built in in the actuato...

Страница 8: ...rminals allowing conductors with a maximum cross section 4 mm2 to be connected Access to the terminal board is obtained after removal of the terminal box cover All control circuits of the electric act...

Страница 9: ...e three phase asynchronous motor 1 drives via countershaft gearing 2 the sun gear of a differential gear unit enclosed in the supporting actuator box power gear transmission 3 In the mechanical power...

Страница 10: ...the transmitter support is positioned at an angle of 180 C with respect to the illustrated position Fig 2a Base plate design with current transmitter 14 66 13 17 67 15 66 16 75 66 12 Legend 12 Torque...

Страница 11: ...direction whereas the segment 24 is designed for the OPEN direction The torque control unit is also fitted with a locking mechanism On operation of the torque limiting switch thismechanism locks this...

Страница 12: ...ranges of adjustment of the signalling switches and the transmitter are required to be changed the position of adjusting wheel K3 should be changed For this purpose the signalling unit should be parti...

Страница 13: ...wheel 62 This wheel is rotated step by step by gear wheels driving cam 57 60 Turning of the cam up to the lever of the CLOSE or OPEN position limit switch PZ or PO causes the switches to change over H...

Страница 14: ...ter 1 x 100 This transmitter has one sided shaft and at its end is fixed a twin wheel 73 composed of gears A and B The principle of drive and transmitter adjustment is equal as at current transmitter...

Страница 15: ...rise up to the resistance value corresponding to the end position open 50 ohms until max 98 ohms Transmitter is set up by this way e Current position transmitters At the first is necessary to set up s...

Страница 16: ...ssary to increase the feeding voltage within the range of recommend values or to decrease total resistance of the current loop R Caution The transmitter CPT 1Az must not be connected without checking...

Страница 17: ...se Press the push button 4 then the push button 20 and keep them depressed until LED blinks When the sense of rotation is changed the end limit positions 4 mA and 20 mA remain valid but the working ra...

Страница 18: ...the actuator is to be stored for a longer period than 3 years then prior to commissioning oil refilling should be made Any manipulation of the equipment at a temperature below 25 C is forbidden Storin...

Страница 19: ...ng to Point 3b Caution The control box cover should be removed so that it is displaced in the direction of extended axis of the actuator output shaft taking care to avoid any damage to the position in...

Страница 20: ...gap that has been thereby disclosed This procedure should be made with the pull rod in the CLOSED position 13 FAILURES AND THEIR REMOVAL Actuator in the end position does not start with motor droning...

Страница 21: ...43 Figs 4 5 6 Type No 52 443 Figs 7 Position transmitter block of local control MODACT MTN MTP actuators 9th place of t no current transmitter 4 20 mA current transmitter 4 20 mA with BMO without BMO...

Страница 22: ...of columns B 150 mm Character on 7th place Ba1I Ba1II Ba1III Ba2I Ba2II Ba2III Bb1I Bb1II Bb1III Bb2I Bb2II Bb2III Bg2I C D E F G H I J K L M P R Spacing of columns Position Closed Thread of coupling...

Страница 23: ...f b ch g e a f b ch g e a 40 a b g a b g max 38 253 max 595 261 max 334 153 100 25 c a d b h g d b h g c a Design 1 M 20 M 20 297 26 A B A B Design 2 Detail of coupling M 20 x 1 5 I M 16 x 1 5 II M 10...

Страница 24: ...g 130 c a 308 d b 352 h g 408 e a 633 f b 677 ch g 733 max 595 max 334 261 325 e a c a d b h g 253 100 153 a b g M20 26 f b ch g 25 215 99 90 e a c a d b h g f b ch g a b g 40 M20 A B Design 1 Detail...

Страница 25: ...ype No 52 443 x1xxx Fig 5 697 436 M30x2 M30 160 261 350 257 835 36 48 60 120 485 376 120 200 with block of terminals with connector External protectivet erminal Local control 697 436 M30x2 M30 160 261...

Страница 26: ...on unit for MODACT MTN MTP 40 electric actuators Type No 52 443 x2xxx design with flange non standard other dimensions and designs of actuators are according to fig 14 15 16 215 160 4x 13 80H8 105 0 2...

Страница 27: ...Q1 MO OPEN torque limit switch SQ2 MZ CLOSE torque limit switch SQ3 PO OPEN position limit switch SQ5 PZ CLOSE position limit switch SQ4 SO OPEN signalling switch SQ6 SZ CLOSE signalling switch SA1 LO...

Страница 28: ...ervomotor MODACT MON MOP Control se styka i a BMO se svorkovnic Wiring diagram of MODACT MTN MTP Control electric actuators with contactors with terminal board P3 0947 Outlet position Control phase BA...

Страница 29: ...servomotor MODACT MON MOP Control se styka i a regul torem ZP2 RE5 se svorkovnic Zapojen elektrick ch servomotor MODACT MON MOP Control se styka i regul torem ZP2 RE5 a BM se svorkovnic with terminal...

Страница 30: ...jumper into clamps t1 t2 Control signal 0 4 20 mA Outlet Position 3 phase motor Brake BR2 blue blue brown brown BRAKE Connect surge voltage protectors to contactor coils O C L R Zapojen elektrick ch s...

Страница 31: ...orem Zapojen elektrick ch servomotor MODACT MON MOP Control se styka i a BMO s konektorem P3 0953 P3M 0954 SA2 O C SA1 L R Wiring diagram of MODACT MTN MTP Control electric actuators with contactors O...

Страница 32: ...iagram of MODACT MTN MTP Control electric actuators with contactors and ZP2 RE5 regulator Wiring diagram of MODACT MTN MTP Control electric actuators with contactors ZP2 RE5 regulator and BMO with con...

Страница 33: ...the control box Sealing ring 60x50 PN 02 9280 2 1 Sealing of output shaft in the control box cover Sealing ring 190x3 PN 02 9281 0 Sealing of control box cover Potentiometer 2 x 100 2340510232 1 Moun...

Страница 34: ...34 NOTES...

Страница 35: ...ary multi turn actuators MODACT MO EEx MOED EEx Explosion proof electric multi turn actuators MODACT MOA Electric multi turn actuators for nuclear power stations application outside containment MODACT...

Страница 36: ...tel 420 321 785 141 9 fax 420 321 785 165 420 321 785 167 e mail zpa zpa pecky cz ZPA Pe ky a s t 5 kv tna 166 289 11 PE KY Czech Republic www zpa pecky cz...

Отзывы: