ZPA Pecky, a.s. 52 442 Скачать руководство пользователя страница 14

14

d)   Rotate the tripping rod 58 at an angle of 90°. As a result, the rod should shift out again. If this is not the case, turn 

the screw 56 or 59 by a small amount.

e)   Readjust the valve to the OPEN position by the required number of revolutions, making use of the actuator.
f)  Depress the tripping rod 58 again in the vertical direction and position it at an angle of 90° on either side.
g)   Turn  the  regulating  screw  59  in  the  direction  of  arrowhead  designated  “O” 

(OPEN) 

till  the  cam  60  depresses  

the spring of microswitch 61 

(OPEN position-limit switch PO).

h)   Rotate the tripping rod 58 at an angle of 90°. As a result, the rod should shift out again. If this is not the case, turn 

the screw 59 or 56 by a small amount.

Note:

Turning the regulating screw 56 or 59 should be stopped at the instant of change-over.
If  the  cams  are  in  the  position  shown  in  Fig.6  before  they  are  adjusted,  or  the  cam  has  already  pressed  down  

the button of the microswitch, the following procedure is used to advantage:

With  the  tripping  rod  58  depressed  and  positioned,  turn  the  adjusting  screw  56  or  59  against  the  direction  of  

the arrowheads till the cam withdraws at its peak from the microswitch lever towards the respective adjusting screw and 
the  microswitch  changes  over,  which  can  be  checked  by  a  suitable  indicating  tester. Then,  move  the  cam  by  turning  
the  adjusting  screw  56  or  59  backwards  in  the  direction  of  the  arrowhead  to  make  the  cam  peak  run  back  on  
the microswitch level till the microswitch changes over again 

(with its button depressed). 

Thus, the adjusting procedure of 

the microswitch has been completed. Finally, shift out the tripping rod 58, as described above.

d)  Resistive position transmitter 1 x 100 

Ω

 

This transmitter has one-sided shaft and at its end is fixed a twin wheel 73 composed of gears A and B. The principle 

of drive and transmitter adjustment is equal as at current transmitter CPT 1Az. The difference is only in sizes of gears A 
and B of twin wheel 73 and as well in the table for working stroke setting.

Resistive position transmitter setting

At the first is necessary to set up suitable gear level from output shaft of actuator to transmitter shaft according to  

a required working stroke of actuator – see following table.

Setting will be done using adjust wheel K3 in gearbox of signalling unit according to previous point b).
Then is necessary to slip in to the shot a necessary wheel of twin wheel, which is fixed on transmitter shaft. Wheel with 

smaller average is signed as A, bigger wheel is signed as B. Adjustment will be done by moving a pad 72, either under the 
transmitter support (in the shot is wheel A) or above the transmitter support (in the shot is wheel B). This will be done in  
a position, when the transmitter support is most away from gearbox. Then screws fixing transmitter support must be slightely 
tighten, so that it is possible to move transmitter support to the position, when wheel A and B is in the shot with driving wheel. 
We will check shot of wheels in this position. Between wheel A (event. B) and driving wheel must be slight will for not to be  
a transmitter shaft tried in perpendicular direction on its axis. Then we will tighten properly by fixing screws of transmitter 
support and and ensure by a varnish. If required working stroke is in overlap of two bands, is more suitable to choose lower band.

Fig.7 -

 

Operating diagram of position-limit switching and signalling switches

 

 

  

Numbers of terminals

 

 

 

Open 

Close

 

on terminal board

 

 

 

 

 

PO

 

 

15-16

 

 

14-15

PZ

 

 

18-19

 

 

17-18

 

Open 

Close

 

 

 

 

 

 

 

 

 

 

 

SO 

 

 

21-22

 

 

 

20-21

SZ  

 

 

24-25

 

 

 

23-24

                     Contact open 

      Contact closed

Содержание 52 442

Страница 1: ...Type numbers 52 442 52 443 Electric Linear Pull rod actuators 4 19 MOUNTING INSTRUCTIONS...

Страница 2: ...ZPA Pe ky a s is certified company in accordance with ISO 9001 as amended...

Страница 3: ...tion or in the tropical atmosphere the anti condensation heater which has been built in all actuators should be always used One or two heater elements should be connected as required Installation of t...

Страница 4: ...tervals The load factor N N R shall be maximum 25 per cent the longest operation cycle N R is 10 minutes The maximum number of switching actions in automatic control mode is 1200 actions per hour The...

Страница 5: ...trol IP 67 Noise Acoustic pressure level A max 85 dB A Acoustic power level A max 95 dB A Tripping thrust At the factory the tripping thrust has been adjusted within the min max range giving in Table...

Страница 6: ...lling switch and the SZ CLOSE signalling switch are used Each of these switches acts only in one direction of output shaft rotation The operating point of the microswitches can be set within the whole...

Страница 7: ...our pole The change over switches are installed in a terminal board box and the control elements on the lid of this terminal board box Position regulator The position regulator built in in the actuato...

Страница 8: ...rminals allowing conductors with a maximum cross section 4 mm2 to be connected Access to the terminal board is obtained after removal of the terminal box cover All control circuits of the electric act...

Страница 9: ...e three phase asynchronous motor 1 drives via countershaft gearing 2 the sun gear of a differential gear unit enclosed in the supporting actuator box power gear transmission 3 In the mechanical power...

Страница 10: ...the transmitter support is positioned at an angle of 180 C with respect to the illustrated position Fig 2a Base plate design with current transmitter 14 66 13 17 67 15 66 16 75 66 12 Legend 12 Torque...

Страница 11: ...direction whereas the segment 24 is designed for the OPEN direction The torque control unit is also fitted with a locking mechanism On operation of the torque limiting switch thismechanism locks this...

Страница 12: ...ranges of adjustment of the signalling switches and the transmitter are required to be changed the position of adjusting wheel K3 should be changed For this purpose the signalling unit should be parti...

Страница 13: ...wheel 62 This wheel is rotated step by step by gear wheels driving cam 57 60 Turning of the cam up to the lever of the CLOSE or OPEN position limit switch PZ or PO causes the switches to change over H...

Страница 14: ...ter 1 x 100 This transmitter has one sided shaft and at its end is fixed a twin wheel 73 composed of gears A and B The principle of drive and transmitter adjustment is equal as at current transmitter...

Страница 15: ...rise up to the resistance value corresponding to the end position open 50 ohms until max 98 ohms Transmitter is set up by this way e Current position transmitters At the first is necessary to set up s...

Страница 16: ...ssary to increase the feeding voltage within the range of recommend values or to decrease total resistance of the current loop R Caution The transmitter CPT 1Az must not be connected without checking...

Страница 17: ...se Press the push button 4 then the push button 20 and keep them depressed until LED blinks When the sense of rotation is changed the end limit positions 4 mA and 20 mA remain valid but the working ra...

Страница 18: ...the actuator is to be stored for a longer period than 3 years then prior to commissioning oil refilling should be made Any manipulation of the equipment at a temperature below 25 C is forbidden Storin...

Страница 19: ...ng to Point 3b Caution The control box cover should be removed so that it is displaced in the direction of extended axis of the actuator output shaft taking care to avoid any damage to the position in...

Страница 20: ...gap that has been thereby disclosed This procedure should be made with the pull rod in the CLOSED position 13 FAILURES AND THEIR REMOVAL Actuator in the end position does not start with motor droning...

Страница 21: ...43 Figs 4 5 6 Type No 52 443 Figs 7 Position transmitter block of local control MODACT MTN MTP actuators 9th place of t no current transmitter 4 20 mA current transmitter 4 20 mA with BMO without BMO...

Страница 22: ...of columns B 150 mm Character on 7th place Ba1I Ba1II Ba1III Ba2I Ba2II Ba2III Bb1I Bb1II Bb1III Bb2I Bb2II Bb2III Bg2I C D E F G H I J K L M P R Spacing of columns Position Closed Thread of coupling...

Страница 23: ...f b ch g e a f b ch g e a 40 a b g a b g max 38 253 max 595 261 max 334 153 100 25 c a d b h g d b h g c a Design 1 M 20 M 20 297 26 A B A B Design 2 Detail of coupling M 20 x 1 5 I M 16 x 1 5 II M 10...

Страница 24: ...g 130 c a 308 d b 352 h g 408 e a 633 f b 677 ch g 733 max 595 max 334 261 325 e a c a d b h g 253 100 153 a b g M20 26 f b ch g 25 215 99 90 e a c a d b h g f b ch g a b g 40 M20 A B Design 1 Detail...

Страница 25: ...ype No 52 443 x1xxx Fig 5 697 436 M30x2 M30 160 261 350 257 835 36 48 60 120 485 376 120 200 with block of terminals with connector External protectivet erminal Local control 697 436 M30x2 M30 160 261...

Страница 26: ...on unit for MODACT MTN MTP 40 electric actuators Type No 52 443 x2xxx design with flange non standard other dimensions and designs of actuators are according to fig 14 15 16 215 160 4x 13 80H8 105 0 2...

Страница 27: ...Q1 MO OPEN torque limit switch SQ2 MZ CLOSE torque limit switch SQ3 PO OPEN position limit switch SQ5 PZ CLOSE position limit switch SQ4 SO OPEN signalling switch SQ6 SZ CLOSE signalling switch SA1 LO...

Страница 28: ...ervomotor MODACT MON MOP Control se styka i a BMO se svorkovnic Wiring diagram of MODACT MTN MTP Control electric actuators with contactors with terminal board P3 0947 Outlet position Control phase BA...

Страница 29: ...servomotor MODACT MON MOP Control se styka i a regul torem ZP2 RE5 se svorkovnic Zapojen elektrick ch servomotor MODACT MON MOP Control se styka i regul torem ZP2 RE5 a BM se svorkovnic with terminal...

Страница 30: ...jumper into clamps t1 t2 Control signal 0 4 20 mA Outlet Position 3 phase motor Brake BR2 blue blue brown brown BRAKE Connect surge voltage protectors to contactor coils O C L R Zapojen elektrick ch s...

Страница 31: ...orem Zapojen elektrick ch servomotor MODACT MON MOP Control se styka i a BMO s konektorem P3 0953 P3M 0954 SA2 O C SA1 L R Wiring diagram of MODACT MTN MTP Control electric actuators with contactors O...

Страница 32: ...iagram of MODACT MTN MTP Control electric actuators with contactors and ZP2 RE5 regulator Wiring diagram of MODACT MTN MTP Control electric actuators with contactors ZP2 RE5 regulator and BMO with con...

Страница 33: ...the control box Sealing ring 60x50 PN 02 9280 2 1 Sealing of output shaft in the control box cover Sealing ring 190x3 PN 02 9281 0 Sealing of control box cover Potentiometer 2 x 100 2340510232 1 Moun...

Страница 34: ...34 NOTES...

Страница 35: ...ary multi turn actuators MODACT MO EEx MOED EEx Explosion proof electric multi turn actuators MODACT MOA Electric multi turn actuators for nuclear power stations application outside containment MODACT...

Страница 36: ...tel 420 321 785 141 9 fax 420 321 785 165 420 321 785 167 e mail zpa zpa pecky cz ZPA Pe ky a s t 5 kv tna 166 289 11 PE KY Czech Republic www zpa pecky cz...

Отзывы: