ZMIO300 Series Hardware Manual Version 1.8
51
not connected, there also no build.
Module type
Index
Input module
(6000 + 10* (expansion address – 1)) h
Output module
(7001 + 10* (expansion address – 1)) h
AD module
(6001+ 10* (expansion address – 1)) h
DA module
(7001 + 10* (expansion address – 1)) h
Expansion example
Like, the local back-level interface of ECAT communication module (ZMIO300-
ECAT) connects with 3 input modules (ZMIO300-16DI), 2 output modules
(ZMIO300-16DO, ZMIO300-16DOP), 1 AD module (ZMIO300-4AD) and 1 DA
module (ZMIO300-4DA) in turn.
→
built data dictionary:
Data dictionary
Remark
5000h
-
5006h
Control index of the first AD module
5007h
Control index of the first DA module
6000h
Status value index of the first input module
6010h
Status value index of the second input module
6020h
Status value index of the third input module
6051h
Status value index of the first AD module
7030h
Status value index of the first output module
7040h
Status value index of the second output module
7061h
Status value index of the first DA module
Data dictionary description of each expansion submodule
Input module
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data
range
Data type
Permissio
n
6000
00
IN_GENERIC
1
1
UNSIGNED 8
Be read