ZMIO300 Series Hardware Manual Version 1.8
42
4
Introductions for Use
4.1
Power Consumption Calculation Example
➢
For coupler module, we select ECAT communication module as the example.
➢
External ECAT communication module is supplied power by 24V, internal coupler
supplies 5V power for each module, the max current output is 2A. Except itself
internal power consumption 1.6W, and it supplies 8.4W power for each expansion
submodule. Please see below form for reference.
4.2
Start Number Configuration
EtherCAT expansion
If coupler uses ECAT communication module, IO start numbers of input module and
output module are configured through bus instruction NODE_IO, AIO start numbers of
AD module and DA module are configured through bus instruction NODE_AIO.
NODE_IO
Grammar
NODE_IO (slot, node) = iobase
Parameter List
slot
Controller bus slot number
Default is 0
node
Device number
Start from 0, 0-
Model
Description
ZMIO300-ECAT
ECAT communication module 1.6W
ZMIO300-16DI
Input module 0.3W
ZMIO300-16DO
Output module (NPN) 0.3W
ZMIO300-16DOP
Output module (PNP) 0.3W
ZMIO300-4AD
AD module 0.4W
ZMIO300-4DA
DA module 0.3W
…
…