UFR1001E
12420-0701-03
Page
5 / 36
www.ziehl.de
11
Sealable LED
Press for > 2 s
Lock / Unlock
LED red
Settings and simulation mode are locked,
While attempting to set,
8
LOc
8
is displayed for 3s
LED green
Setting and simulation enabled
4. Detailed description
4.1
Description of the connections
Connection
Description
A1 and A2
Rated control supply voltage Us, see
Technical Data
11, 12, 14; 21, 22, 24
Relay K1 and K2
E1
– E2
Enable
– Input
Volt-free contact
8
vsr .
8
8
off.
8
, no function
8
vsr .
8
8
on.
8
, E1-E2 closed: Vector shift active but not evaluated,
monitoring of feedback contacts off for use with generator (mains
synchronization)
8
vsr .
8
8
stby.
8
, E1-E2 closed: K1 and K2 off (standby), vector shift off
8
vsr .
8
8
Y1Y2.
8
, E1-E2 closed: Feedback contacts no evaluated, vector
shift off, when using with generator (mains synchronization)
Y0, Y1, Y2
Inputs, feedback contacts
Volt-free n/o or n/c contact, self-learning when switching on
Set value > turn-on time section switch under
8
rel .
8
8
trel.
8
/ can
switch-off if not connected or if external devices/switches can activate the
section switch (
8
off .
8
)
I1
Supply voltage for digital outputs, max. 27 V DC
Q1…Q4
Digital output over-/undervoltage/-frequency, Q3 + Q4 = ROCOF
Q5
Digital output error, in Program 3-6 additionally the 2nd threshold value
L1, L2, L3, N
Phase L1, L2, L3 and neutral conductor
4.2
Functional characteristics
Functional characteristics
Explanation
VSR display value
The highest measured value is always displayed. The display value is reset
to 0 by deleting the max. value and when resetting into the go (good) state.
Delay Enable On time
Runs down when starting the unit and after opening the enable input; during
this time there is no evaluation of the vector shift
Reset time
When a reset time
8
dof
8
is running, it is always counted down in the
display (shortest one first)
Reset
Use the Reset key or interrupt the control voltage for > 2 s (comply with reset
delay)
Display mode
8
Scn
8
After the last measurement it switches into the scan mode; this is indicated
by the display
8
scn
8
.
All measurements will now be displayed cyclically for the time set in
8
dit
8
.
MIN / MAX values
All min and max values are saved zero-voltage maintained (non-volatile).
Tripping time
(only with feedback
contacts connected)
Connecting the feedback contacts enables measuring the shut-down time.
After a tripping time with the test button it is displayed until a button is
pressed again with a resolution of up to 1ms.
Total shut-down time = Tripping time + Response time
8
dal.
8
Содержание UFR1001E
Страница 28: ...UFR1001E 12420 0701 03 Page 28 36 www ziehl de 14 Verification of conformity ...
Страница 29: ...UFR1001E 12420 0701 03 Page 29 36 www ziehl de ...
Страница 30: ...UFR1001E 12420 0701 03 Page 30 36 www ziehl de ...
Страница 31: ...UFR1001E 12420 0701 03 Page 31 36 www ziehl de ...
Страница 32: ...UFR1001E 12420 0701 03 Page 32 36 www ziehl de ...
Страница 33: ...UFR1001E 12420 0701 03 Page 33 36 www ziehl de ...
Страница 34: ...UFR1001E 12420 0701 03 Page 34 36 www ziehl de 15 Unbedenklichkeitsbescheinigung ÖVE ÖNORM E 8001 4 712 ...