3. Display and controls
1
Test button
Press
briefly
Output relays de-energize immediately. If Y1+Y2 are connected and the feedback signal
is activated, the tripping time is displayed until the next time a button is pressed
2
LEDs frequency / voltage limit value undercut / exceeded
(red)
On,
8
AL
8
or
8
AL M
8
Limit value undercut / exceeded
FLASHES,
8
AL
8
or
8
AL M
8
Reset delay
8
dof
8
counting down
3
LED vector surge
(VSR, red)
ON,
8
AL
8
Threshold value for vector shift exceeded
FLASHES,
8
AL
8
Reset delay
8
dof
8
counting down
4
LEDs relay status
(yellow)
OFF
Relay is released
ON
Relay operating
5
Digital display 4-digits
(red)
Depending on program, display of current voltage, frequency, vector shift, average value
Displays the alarm signals, e.g.
8
AL
8
,
8
aL M
8
Displays the errors with error code e.g.
8
Err9
8
6
LED Time
(yellow)
ON
A time is displayed
7
Last decimal point
(red)
OFF
Display mode
Illuminated
Menu mode
Flashes
Configuration mode
8
Set/Reset key
(in display mode, normal state)
Press briefly
Display of next measured value / alarm counter
Press for > 2 s
Reset, quit error messages
Press for > 4 s
Displays the program, e.g.
8
Pr 1
8
Press for > 10 s
Displays the software version, e.g.
8
0-04
8
9
Up / Down key
(in display mode, normal state)
Press briefly
Change to the menu mode, display of alarm memory (Down) / cumulative time
of alarms, standby counter, standby time (Up), pushing Set button for ≥ 2 s
resets the stored values
Press for > 2 s
Display of MAX (Up) / MIN (Down) - measured values, additional pushing of Set
button for ≥ 2 s deletes the stored values
10
LEDs measurement allocation
(yellow)
LEDs
Measured value
Lx and N ON
Voltage value (L1 against N, L2 against N, L3 against N)
Lx and Ly ON
Voltage value (L1 against L2, L2 against L3, L1 against L3)
Lx FLASHING quickly
Vector surge (L1, L2, L3)
L1 FLASHING
Frequency
Содержание UFR1001E
Страница 28: ...UFR1001E 12420 0701 03 Page 28 36 www ziehl de 14 Verification of conformity ...
Страница 29: ...UFR1001E 12420 0701 03 Page 29 36 www ziehl de ...
Страница 30: ...UFR1001E 12420 0701 03 Page 30 36 www ziehl de ...
Страница 31: ...UFR1001E 12420 0701 03 Page 31 36 www ziehl de ...
Страница 32: ...UFR1001E 12420 0701 03 Page 32 36 www ziehl de ...
Страница 33: ...UFR1001E 12420 0701 03 Page 33 36 www ziehl de ...
Страница 34: ...UFR1001E 12420 0701 03 Page 34 36 www ziehl de 15 Unbedenklichkeitsbescheinigung ÖVE ÖNORM E 8001 4 712 ...