UFR1001E
12420-0701-03
Page
18 / 36
www.ziehl.de
8.10 Alarm memory
Independent of the alarm counter, the UFR1001E stores the most recent 100 shut-down causes (cause,
measurement value, at operating time). Simulated alarms are also registered. The LEDs indicate the cause;
the tripping value that led to the alarm each stands in the 7-segment display. Alternative to that
the time is shown in hours which have passed since the last tripping (with applied control voltage).
These values remain saved even after the power has been turned off.
Query alarm memory:
Change into the display mode
Press the button several times
display
8
ac
xx
8
Press the
button 1x
display
8
x
.
xx
8
/
8
x
.
xx
8
(tripping value or error no. / time that has passed in hours)
Press the
button 1x, go to next alarm
The alarm memory is only deleted during a program change.
8.11 Standby counter and standby time
The standby counter
8
stby
8
, is increased by 1 with every standby shut-down. Up to 9999 shut-downs are
counted. That lets the UFR1001E quickly detect how often, e.g., shut-down was performed through a ripple
control receiver.
Query the standby counter:
Change into the display mode
Press the button several times until
display
8
ac
xx
8
Press the
button 2x
display
8
stby
8
/
8
xxxx
8
The standby time
8
stby
8
indicates how long the relay was switched off by the standby mode. It is recorded
with a resolution of 1 minute and only when the control voltage is applied and if no alarm is present.
Query the standby time:
Change into the display mode
Press the button several times until
display
8
ac
xx
8
Press the
button 3x
display
8
stby
8
/
8
x
.
xx
8
(Time LED is illuminated)
Delete the standby counter and standby time (only together):
Display alarm counter
8
ac
xx
8
Press the
button 2x
display
8
stby
8
/
8
xxxx
8
Keep the button pressed for 2s until
display
8
stby
8
/
8
0
8
Содержание UFR1001E
Страница 28: ...UFR1001E 12420 0701 03 Page 28 36 www ziehl de 14 Verification of conformity ...
Страница 29: ...UFR1001E 12420 0701 03 Page 29 36 www ziehl de ...
Страница 30: ...UFR1001E 12420 0701 03 Page 30 36 www ziehl de ...
Страница 31: ...UFR1001E 12420 0701 03 Page 31 36 www ziehl de ...
Страница 32: ...UFR1001E 12420 0701 03 Page 32 36 www ziehl de ...
Страница 33: ...UFR1001E 12420 0701 03 Page 33 36 www ziehl de ...
Страница 34: ...UFR1001E 12420 0701 03 Page 34 36 www ziehl de 15 Unbedenklichkeitsbescheinigung ÖVE ÖNORM E 8001 4 712 ...