UFR1001E
12420-0701-03
Page
36 / 36
www.ziehl.de
17. Adjustment values table VDE-AR-N 4105, Low Voltage Pr 1+2
Protective function
AR
4105
ZIEHL in * Un
in % Un
Adjustment
value
Tripping
time
dAL
OFF-delay
time
doF
Voltage decrease protection
U<
U_
0.8 * Un 80 % Un
184 V
100 ms
60 s
Voltage increase protection
(10-minutes mean value)
U>
UM
1.1 * Un 110% Un
253V
100 ms
60 s
Voltage increase protection
U>>
U,
1.15 *
Un
115% Un
264V
100 ms
60 s
Frequency decrease
protection
f<
F_
47.5Hz
100 ms
60 s
Frequency increase protection
f>
F,
51.5Hz
100 ms
60
18. Adjustment values table BDEW June 2008, acc 3.2.3.3-1,
Medium Voltage Pr 3-6
Function
Adjustment range
of the protective
relay
Default settings
Voltage increase protection U>>
1.00
– 1.30 U
n
1.15 U
n
100 ms
Voltage increase protection U>
1.00
– 1.30 U
n
1.08 U
n
60 s
Voltage decrease protection U<
0.15
– 1.00 U
n
0.80 U
n
2.7 s
Voltage decrease protection U<< *
0.15
– 1.00 U
n
0.45 U
n
300 ms
Frequency increase protection
f>
50.0
– 65.0 Hz
51.5Hz
100 ms
Frequency decrease protection
f<
45.0
– 50.0 Hz
47.5Hz
100 ms
* Not enabled in as delivered condition
Содержание UFR1001E
Страница 28: ...UFR1001E 12420 0701 03 Page 28 36 www ziehl de 14 Verification of conformity ...
Страница 29: ...UFR1001E 12420 0701 03 Page 29 36 www ziehl de ...
Страница 30: ...UFR1001E 12420 0701 03 Page 30 36 www ziehl de ...
Страница 31: ...UFR1001E 12420 0701 03 Page 31 36 www ziehl de ...
Страница 32: ...UFR1001E 12420 0701 03 Page 32 36 www ziehl de ...
Страница 33: ...UFR1001E 12420 0701 03 Page 33 36 www ziehl de ...
Страница 34: ...UFR1001E 12420 0701 03 Page 34 36 www ziehl de 15 Unbedenklichkeitsbescheinigung ÖVE ÖNORM E 8001 4 712 ...