Limits
P(t<3s) S2 off
Pr7+8: Power limit of the 2nd level S2 (the
2nd switching point) of the Pav,e monitoring
-
999.99…0.00
kW
P(t=0s) S3 off
Pr7+8: Power limit of the 3rd level S3 (the
3rd switching point) of the Pav,e monitoring
-
999.99…0.00
kW
f-rejection
Pr7+8: Frequency rejection active = Pav,e
monitoring inactive when the line frequency
f < 49,8 Hz or f > 50,2 Hz
on / off
Digital
inputs
Y0-Y1
When digital input Y1 is closed, each relay
can be individually being switched on / off or
all relays on / off
K1 on / K1 off /
K2 on / K2 off /
K3 on / K3 off /
K1-3 on /
K1-3 off /
Aout I 100% /
Aout I 0% /
Aout U 100% /
Aout U 0%
See “
Y0-Y2,
Y2 overwrites Y1
When digital input Y2 is closed, each relay
can be individually being switched on / off or
all relays on / off
Y0-Y3,
Y3 overwrites Y2
When digital input Y3 is closed, each relay
can be individually being switched on / off or
all relays on / off
Y0-Y4,
Y4 overwrites Y3
When digital input Y4 is closed, each relay
can be individually being switched on / off or
all relays on / off
Menu
Parameters
Explanation
Adjustment
range
Analogue
output U
Function
Analogue output as a transducer
(measurement converter) (kW-Lx) or as a
control output (Load-Lx) for, e.g., linear
phase angle control
off / kW-L123 /
kW-L1 / kW-L2 /
kW-L3 / Load-
L123 / Load-L1 /
Load-L2 / Load-
L3
Mode
0 or 2 V or individual
… 10 V
0…10 V / 2-10 V /
ind. ZP
Zero point
(transducer
(measurement
converter))
Power in kW for zero point,
Power in kW for full-scale
-
: Feed-in (export) (excess)
+
: Draw (import
= purchase)
(Zero point and full-scale may also have
different signs)
-
999,99…999,99
kW
Full-scale
(transducer
(measurement
converter))
-
999,99…999,99
kW
Individual zero
point
Individual zero point, this is the smallest
value which is controlled on the analogue
output
0 … 5 V
Set point
(Load / Control)
With sufficient load regulates the analogue
output to this value
-
999,99…999,99
kW
Max. power
(Load / Control)
Max. power consumption of the controlled
load at 10 V
0,1…500,00 kW
Control
speed
Slow (20%)…fast (90%),
Control response = (difference between the
set point-
actual value) * 20…90%
20…90 %
Control interval
The set point value is readjusted in this
interval; fast (0.5s) … slow (60.0s)
00,5…60,0 s
Control tolerance
Difference set point actual > Control
tolerance = Failure of the load is detected,
e.g. due to a thermostat being switch-off;
load on the analogue output is not taken into
account by K1-3 when additional loads are
switched on
5…50 %