EFR4001IP
12720-0713-00
Page
27 / 53
www.ziehl.de
8
Commissioning
8.1 Information on operating
8.2 Switch on the unit / Language selection / Time setup
During the initial start, the unit displays the language selection, followed by the time setup (date and time).
Once the language has been selected and the time has been set, the monitoring starts. The language can be
changed at any time in the menu (
Settings -> language
). The date and time can be changed at any time in the
menu (
Settings -> date, time
). They can also be synchronized with a timeserver over ethernet by setting the
function "timeserver" as ON under
Web Server -> Network -> Timeserver settings
.
8.3 Device in the network
If the EFR4001IP is connected to a network via ethernet, the display of the measured values and the
parameterization can be performed via a web browser on the computer. Basic knowledge of network
technology is required for the configuration.
8.3.1 Find the device in the network
Network with DHCP server:
After connecting to the network, the device automatically receives an IP address.
Query IP address on the device:
•
In menu mode, select the menu item “Network”
•
Settings for the network parameters DHCP, IP address and subnet mask can be viewed and changed.
Set network with DHCP server / manual IP address:
The relevant network parameters can be set and changed directly on the device:
•
In menu mode, select the menu item “Network”
•
Make settings for the network parameters DHCP, IP address and subnet mask.
Connection:
Start web browser on computer and enter the IP address in the address bar.
8.3.2 Call via web browser
After calling the IP address, the device logs in the web browser. For description, see
“14 Webserver”.
confirm,
move / scroll right
Increase value,
move / scroll up,
Min/Max value, 2s Reset
back,
move / scroll left
Decrease value,
move / scroll down,
2s Menu