EFR4001IP
12720-0713-00
Page
21 / 53
www.ziehl.de
7.10 Program 6 (zero export / import device phase-wise, prevent/ limit infeed)
Precondition:
•
Own generating unit, e.g. photovoltaic, CHP, wind rotor, water turbine, …
•
Regulatory requirements from the grid operator for limitation or prevention of energy flow in
one of the
three phases
.
Goals:
•
Prevent grid-infeed of mixed- or non-self-generated energy.
•
Charging of batteries only in case of excess power and discharge during delivery (=import= draw)
only.
•
Prevent or limit feed in of energy
•
Limit feed into maximum permissible value
•
If necessary, switch on consumers before the generating unit has to be limited or shut down.
Measurement:
•
The monitored phase can be selected for each alarm/relay independently. In case of setting L123, it is
monitored if the limit is reached in at least one phase (OR).
•
The EFR4001IP monitors the flow of energy at the grid connection point.
(Import (purchase) from or export (delivery) to the public power grid)
•
The EFR4001IP monitors the flow of energy in front of batteries directly.
(Prevent energy flow in inadmissible direction)
Feature:
•
The actual measured power P L1, P L2, P L3 or P L123 as assigned to the alarms/relays is evaluated
.
•
The monitoring function is determined separately for each alarm/relay via the set limit values
MAX monitoring: Power Kx off > Power Kx on;
MIN monitoring: Power Kx off < Power Kx on.
•
Fixed function of relay: alarm = relay off = contact x1-x4 open, contact x1-x2 closed.
•
Storage of shut down (autoreset on = switched off), reset at device or disconnect Us.
•
The three relay outputs (alarms) work independently of each other.
•
Delay-OFF times can be set from 0 s (= reaction time <500 ms.)
Switch-off MAX monitoring:
•
If the power in the assigned phase rises above the limit Kx off, the delay-OFF time starts to count. If
the power stays above the limit for this delay-OFF time, the relay Kx switches off.
•
Reconnection: If the power in the assigned phase falls under the limit Kx on, the set delay-ON time
starts to count. If the limit value remains undercut for the entire delay-ON time, the relay Kx switches
on (after reset only when auto Reset Kx = off).
Switch-off MIN monitoring:
•
If the power in the assigned phase falls below the limit Kx off, the delay-OFF time starts to count. If the
power stays below the limit for this delay-OFF time, the relay Kx switches off.
•
Reconnection: If the power in the assigned phase rises above the limit Kx on, the set delay-ON time
starts to count. If the limit value remains exceeded for the entire delay-ON time, the relay Kx switches
on (after reset only when auto Reset = off).
Examples:
•
Limitation of grid-infeed:
Own-generating unit produces more power than permissible at the grid-connection point:
EFR4001IP switches on 1 or 2 consumers. If this is not sufficient, the generation is reduced or
switched off.
•
Zero-grid-infeed: It is not allowed to feed into the grid.
EFR4001IP switches on 1 or 2 consumers. If this is not sufficient, the generation is reduced or
switched off.
•
Storage without import:
EFR4001IP shuts down the unit, in case of power flow in inadmissible direction (to battery).
•
Storage without delivery to grid (zero export):
EFR4001IP shuts down the unit, in case of power flow in inadmissible direction (to grid).