4 Mounting
4.1 General notes
Attention!
•
Before installation remove the device from the packing and check for any possible
shipping damage! Start-up is not allowed in the case of transport damage!
•
Do not mount equipment on vibrating base!
•
When mounted onto lightweight walls, there must be no impermissibly high vibrations
or shock loads. Any banging shut of doors that are integrated into these lightweight
walls, can result in extremely high shock loads. Therefore, we advise you to decouple
the devices from the wall.
•
Do not allow drilling chips, screws and other foreign bodies to reach the device
interior!
•
The device should be installed in a location where it will not be disturbed, but at the
same time can be easily accessed!
•
Care must be taken to avoid direct radiation from the sun!
•
The device is designed for vertical installation (bottom cable inlet). A horizontal or
reclined installation is only permissible after technical release of the manufacturer!
•
Use the templates printed on the device packing to mark the fastening bore holes.
•
Assemble the device on a clean and stable base. Do not distort during assembly! Use
the appropriate mounting devices for proper installation of the unit!
•
Two lines may only be fed through one cable gland with the sealing insert for two
lines.
•
Remove the connection cover for mounting and connection, and subsequently close
it again carefully.
Drilling template on packing
G
e
h
ä
u
se
h
o
u
si
n
g
1
1
1
mm
Gehäuse /
housing
106 mm
1
1
mm
8
3
mm
91 mm
Schraube
max 4,5 mm
screw max
4,5 mm
Bohrschablone
drilling template
Vertical mounting
1
Lid screw (tightening torque 1.1 Nm)
2
Cable gland M16 + seal insert with two holes
(5 mm)
Operating Instructions
UNIcon
CTG-150AVC
Mounting
L-BAL-E287-GB 2015 Index 004
Part.-No.
6/36