8 Programming
8.1 Base setup
8.1.1 BASE SETUP
2.01
Mode
2.00
: Temperature sensor
2.01
: Temperature controller output 0...10 V (factory setting)
2.03
: Temperature controller output 0...10 V and two-position controller via
relay
°
C
Units
Display in SI-unit "
°
C" (factory setting) or Imperial- unit (US) "
°
F".
Conversion factor:
Temperature: t /
°
F = 1.8 x t
°
C + 32
Settings for temperature differences (with SI units in K) are also made for
Imperial units (US) in
°
F (
Δ
1.8
°
F
Δ
1 K ).
KTY81-210
Sensortype
Sensor type: KTY 81-210 (factory setting) or PT 1000.
-50.0
°
C
(-58.0
°
F)
Range Min. Temp.
Setting measuring range, minimum temperature value (only for
2.00
)
Setting range:
-50.0...150.0
°
C
(-58.0...302.0
°
F)
Factory setting:
-50.0
°
C
(-58.0
°
F)
150.0
°
C
(302.0
°
F)
Range Max. Temp.
Setting measuring range, maximum temperature value (only for
2.00
)
Setting range:
150...-50
°
C
(302.0...-58.0
°
F)
Factory setting:
150.0
°
C
(302.0
°
F)
0.0 K
(0.0
°
F)
Offset
Adjustment temperature sensor
Setting range: -20.0...20.0
°
C
(-36.0...36.0
°
F)
Factory setting: 0.0 K
(0.0
°
F)
OFF
MSCO
Minimum air switch-off (only for
2.01
+
2.03
)
|
MSCO
|
:
|
OFF
|
(factory setting)
If
“
Min. Uout
”
is adjusted (e.g. 2.0 V), than no diconnection of the output takes
place (does not go under
“
Min. Uout)
”
.
|
MSCO
|
:
|
-2.0 K
|
(example)
It takes place a disconnection from Setting
“
Min. Uout
”
to
“
0
”
, if the given
difference is reached related to the Setpoint.
At a plus value (+) before reaching the desired value.
At a minus value (-) after falling below the desired value.
Hysteresis
|
H
|
ON /OFF: approx. 1 K
(1.8
°
F)
Setting range:
-10.0 K...+10.0 K
(-34.4...+32.4
°
F)
Operating Instructions
UNIcon
CTG-150AVC
Programming
L-BAL-E287-GB 2015 Index 004
Part.-No.