If "Level min." is higher than "Level max." , the "Level max." switching point is without hysteresi.
8.5.2 Limit message temperature
Menu overview
Function
Designation
OFF
Actual Temp Fnc
OFF: no function
ON: limit message active
The values "Temp min." and "Temp max" can be set independent of each
other.
The "Limit Temp." message appears in the display if the set limits for the
temperature are exceeded or undershot.
The message via the relay depends on the programmed function (see IO
Setup), with the factory setting (K1 function =
|
2K
|
, not inverted), the relay is
de-energised in case of a message (terminals 13 - 14 disconnected).
-50.0
°
C
(-58.0
°
F)
Temp min.
Work can be carried out with one as well as with both limit indicators.
If the actual value undercuts the set value "Temp min.", this is reported until
the set value (plus 5 % hysteresis) has been exceeded once again.
If the actual value exceeds the set value "Temp max.", this is reported until
the set value (minus 5 % hysteresis) has been undercut once again.
150.0
°
C
(302.0
°
F)
Temp max.
2 s
Temp delay
The indication is delayed by the time set.
Setting range: 0 - 120 sec.
Factory setting: 2 sec.
Operating Instructions
UNIcon
CTG-150AVC
Programming
L-BAL-E287-GB 2015 Index 004
Part.-No.
28/36