7.3 Menu structure
27.5
°
C
Actual Value
Display after turning on the voltage supply.
Switch over between actual value display and
“
INFO
”
with
the key shortcut for Escape (Esc =
▼
+
▲
).
INFO
Selection of the menu group (e.g. BASE SETUP) to the right through the
▼
-key, to the
left through the
▲
-key.
Youcangotothemenuitemsinthe
menu
groups (e.g. mode) by using the P key. Use the
arrow keys to move up and down within the menu group.
To make adjustments, press the
P
key after selecting the menu item. If the previously set
value starts to
fl
ash, it can be adjusted with the
▼
+
▲
keys and then saved with the
P
key. To exit the menu without making any changes, use the
“
Esc
”
short-key, i.e., the
originally set values remain.
Example for Mode
2.01
(Factory setting)
INFO
▼
▲
SETTING
▼
▲
BASE SETUP
P
↓
↑
ESC
P
↓
↑
ESC
P
↓
↑
ESC
20.0
°
C
Actual value
20
°
C
Setpoint 1
2.01
Mode
▲
▼
▲
▼
▲
▼
20.0
°
C
Setpoint 1
15
°
C
Setpoint 2
°
C
Units
▲
▼
▲
▼
▲
▼
0.0 V
Uout
5.0 K
Pband
KTY81-210
Sensortype
▲
▼
▲
▼
▲
▼
2058
Ω
Resistor
0.0 V
Min. Uout
0.0 K
Offset
▲
▼
▲
▼
▲
▼
0.08
UNIcon
10.0 V
Max. Uout
OFF
MSCO
Reprogramming Mode
2.01
to
2.00
in
“
BASE SETUP
”
1
2
3
4
5
6
7
2.01
Mode
P
«
2.01
»
Mode
▲
«
2.00
»
Mode
P
2.00
Mode
Operating Instructions
UNIcon
CTG-150AVC
Modes/Start-up
L-BAL-E287-GB 2015 Index 004
Part.-No.
14/36