8.4.4.3
External message, function
|
2D
|
Connection of an external fault indication - the device continues operating with no
changes after a message and
“
External Error
”
appears in the display. Message via relay
“
K1
”
depending on programmed function (see digital output
“
DO
”
).
A programmed alarm relay (factory set
“
K1 function
”
=
|
2K
|
) does not report the switch-
off.
100 Pa
27.1
°
C
External message display alternating with the
actual value display
External Error
27.1
°
C
Possible controls
Real input
Inverting DI
State input
External Error
Digital input D1 (terminals: 1, 2)
OFF
Voltage ON
YES
Voltage OFF
NO
ON
Voltage ON
NO
Voltage OFF
YES
Timer from time switch
OFF
Timer active
YES
Timer not active
NO
ON
Timer active
NO
Timer not active
YES
MODBUS interface (terminals: A, B)
OFF
Register H01 Bit 15 not set
NO
Register H01 Bit 15 set
YES
ON
Register H01 Bit 15 not set
YES
Register H01 Bit 15 set
NO
8.4.4.4
Setpoint 1/2, function
|
5D
|
Switching between control with Setpoint 1 and Setpoint 2.
Setpoint 1active
Setpoint 2 active
21.8
°
C
Actual Value
The active Setpoint is indicated in the menu
INFO, an active
“
Setpoint 2
”
is signalized by the
moon symbol.
17.6
°
C
Actual Value
Operating Instructions
UNIcon
CTG-150AVC
Programming
L-BAL-E287-GB 2015 Index 004
Part.-No.
26/36