8.4 Menu group "IO SETUP"
8.4.1 Allocation: virtual IOs/real IOs
A distinction is made between virtual inputs/outputs (IOs) and actual inputs/outputs
(IOs).
•
Actual IOs are physical inputs, physical outputs and timer functions.
•
Virtual IOs are the inputs and outputs used to make the settings.
Example of possible assignments from actual to virtual IOs
Virtual IOs
Pool real IOs (signal sources)
AO1
Analog output
•
Analog output A1 (terminals: A, GND)
DO1
Digital output
•
Relay output K1 (terminals: 13, 14)
DI1 - DI3
Digital inputs
(for
2.00
not available)
•
Digital input D1 (terminals: 1, 2)
•
Timer from time switch
•
MODBUS interface (terminals: A, B)
If only one signal source is available, no further assignment is possible (n.a. = no assignment).
8.4.2 Analog output
“
AO
”
Menu overview
Function
Designation
Control sign. 2A
AO1 Function
Setting of the desired function (see following table).
A1
AO1 Signal
Analog output A1 (terminals: A, GND)
No further assignment possible, n.a. (no assignment) = No signal assigned.
OFF
AO1 Inverting
Inverting output
Setting of the desired function
Function
Designation
OFF
No function
Control sig. 2A
Control signal (factory setting)
MODBUS sig. 17A Setting via MODBUS register
Operating Instructions
UNIcon
CTG-150AVC
Programming
L-BAL-E287-GB 2015 Index 004
Part.-No.
21/36