Figure 4: Text output
Use the hot key "Ctrl" + "F" to switch to "Stdio: Both".
Text input "d" Debug function activated, text output during running communication.
Text input "D": Text output stopped.
6.7MODBUS: Timeout
In the
le "Chip.ini", on the Drive A of the Gateway, the timeout can be set. The Factory
setting is 500 (500ms). The "Chip.ini" can be changed with CHIPTOOL.
[NCGATEWAY]
TIMEOUT1=500
Timeout channel 1
TIMEOUT1=500
Timeout channel 2
TIMEOUT1=500
Timeout channel 3
TIMEOUT1=500
Timeout channel 4
TIMEOUT1=500
Timeout channel 5
TIMEOUT1=500
Timeout channel 6
TIMEOUT1=500
Timeout channel 7
TIMEOUT1=500
Timeout channel 8
TIMEOUT1=500
Timeout channel 9
If a node is not reached after the set timeout, the
“
exception code
”
0x0B is issued.
Is the transaction buffer (max. 20 transactions per channel can be buffered) at the limit,
the
“
exception code
”
0x0A is issued.
The timeout on the client side must be higher than the timeout of the gateway. We
recommend a client timeout of 2 x Gateway timeout
Operating Instructions
NETcon
–
model series DIG-9NE
Communication
L-BAL-E134-GB 1118 Index 001
Part.-No. 00163363-GB
17/21