Example of a channel with the integrated fail safe termination in the Gateway
NETcon MB/TCP
Gateway
150 Ohm
Max 63 FFU
499
150
499
A
B
+
-
The data line must be connected from one device to the next (daisy chain). No other
type of wiring topology is allowed!
Auto addressing is not possible when using a repeater because the auto addressing
function is not forwarded by the repeater.
In addition, a network termination (150
Ω
) should be used at the end of every channel.
Networking with RJ45 patch cable by usage connection box for ECblue
11.04.2011
v_modbus_net_autoadr_gateway.vsd
4...63
1
BUS1
BUS2
2
BUS1
BUS2
3
BUS1
BUS2
RJ45
RJ45
RJ45
Gateway
Traf
c-LEDs
A Operation LED (orange)
B 1 - 9 Traf
c LED (green). Indicates the channel activityby
ashing faster or slower. LED
permanent on --> No communication with the corresponding channel.