12.4.2
FTET6/10AHMQ-L: Central exhaust air with activation of group 2
16.05.2011
v_ftet-l_zentralabl.VSD
K 0...10 V
K 0...10 V
K 0...10 V
K 0...10 V
K 0...10 V
K 0...10 V
1
2
3
4
5
6
TFR
TFR
TFR
TFR
TFR
TFR
CTE/AH(X)-L
2
CTE/AH(X)-L
3
CTE/AH(X)-L
4
CTE/AH(X)-L
5
CTE/AH(X)-L
6
H
ON/OFF
Bus
Bus
S-ET10
ZL_TFR
FTET6AHMQ-L
1
1~ Asyn
0...100 %
1~ Asyn
ON/OFF
Terminal assignment of controllers for 6 compartments
Legend
Component
Terminal
Information
1 ~ Asyn
0...100 %
Exhaust fan
PE, U1-U2
TB-TB
At device 1 (type FTET) = master
Continuous speed control of extractor fan via frequency
inverter type FTET. Motor protection via
“
TB
”
connec-
tion.
Master for bus and control of cot 1.
2.G 1~ Asyn
ON / OFF
second Group
Fault indication
31-32
D1-D1
At device 1 (type FTET) = master
Activation, second group
Fault indication from motor protection unit S-ET10
Z - TFR
Sensor supply air
E2-T2
At device 1 (type FTET) = master
TFR
Sensor cot
E1-T1
E1-GND
At device 1 (type FTET) = master
at devices 2...6 (type CTE/AH-L) = slaves
Z - TFR
Sensor supply air
E2-T2
At device 1 (type FTET) = master
K 0...10 V
Exhaust air
fl
ap 0...10 V
A1-GND
For all devices 1...6
H ON/OFF
Heating (two-point)
21-24
At device for cot 3
Bus
Bus connection
A (D+), B (D-), GND
Connect all devices 1...6
Line connections and external fault indication not considered!
Programming of the controllers
Device
Cot
Installation
menu
Designation
factory
setting
Setting site
Information
1
Ventilation
Exhaustair rate
10 %
16.6 %
For calculation of total exhaust air
Exhaust sys-
tem
Exhaust mode
OFF
1
1 = relation to central exhaust air total
Group version
OFF
2
Connection of the group by relays
Bus
Bus mode
0
1
Device is MODBUS master
Address
32
- - -
1
- - - - stands automatically for address 1 of the
master
Number slaves
- - - -
5
Number of connected Slave controllers
IO Setup
Freshairtemp.
Bus
E2
Sensor supply air at
“
E2
”
output U1-U2
0
7
controlled group 1 for central exhaust air
Relays K3
4
8
Switch on group 2 for central exhaus air
K3 Antiblock
OFF
ON
Anti block protection for group 2 activated
D1 Function
OFF
|
1D
|
or
|
7D
|
Fault indication from S-ET10 at device 1 for
|
7D
|
message also if
“
cot OFF
”
2...6
Ventilation
Exhaustair rate
10 %
16.6 %
For calculation of total exhaust air
Bus
Address
32
2 / 3 / 4 / 5 / 6
Bus address for controller 2, 3, 4, 5, 6
Attention! Total exhaust air may not be greater than 100 %!