background image

Group2(8)

Group2(8)

Setting range Address: OFF-1...31 (Factory setting: OFF)
Setting range Function: K1 - K2 - K3 - PWM * - A1 - A2 - A3

Gruppe3 (9)

Group3(9)

Setting range Address: OFF-1...31 (Factory setting: OFF)
Setting range Function: K1 - K2 - K3 - PWM - A1 - A2 - A3 -

Group4 (10)

Group4(10)

Setting range Address: OFF-1...31 (Factory setting: OFF)
Setting range Function: K1 - K2 - K3 - PWM * - A1 - A2 - A3

Group5 (11)

Group5(11)

Setting range Address: OFF-1...31 (Factory setting: OFF)
Setting range Function: K1 - K2 - K3 - PWM * - A1 - A2 - A3

Freshairsh.(12)

Freshairshutter (12)

Setting range Address: OFF-1...31 (Factory setting: OFF)
Setting range Function: K1 - K2 - K3 - PWM * - A1 - A2 - A3

Freshairfan(13)

Supply air fan (13)

Setting range Address: OFF-1...31 (Factory setting: OFF)
Setting range Function: K1 - K2 - K3 - PWM * - A1 - A2 - A3

Heatex. bypass(14)

Heat exchanger  Bypass(14)

Setting range Address: OFF-1...31 (Factory setting: OFF)
Setting range Function: K1 - K2 - K3 - PWM * - A1 - A2 - A3

Group1(7)

Example: Switch on group1 by member (Address) 3 with relays K1

network user 3 in bus system
Function 7 in IO Setup for group1
Relays K1

In the slave the appropriate output must have the function 

17

Functions of the group control which are distributed from the master to slave devices. 
After selecting the user (1..32) this is con

rmed with the 

P

 -key. Then the output on 

which the function works is set. 

Selection:

Relays: K1, K2, K3
PWM signal: PWM *
0 - 10 V Signal: A1, A2, A3 

 

* PWM output only available for device types CTE/AH-L and PTE-6/10AHQ-L

Buserror

Buserror

Number of bus errors occurred

Bus CRC-Errors

Bus CRC-Errors

Number of Bus CRC-Errors

Operating Instructions 

Fcontrol

 

 model series FTET4/6/10AHMQ-L

The Installation menu

L-BAL-E139-GB 2022/03 Index 006

Part.-No. 

36/92

Содержание Fcontrol FTET4AHMQ-L

Страница 1: ...6 10AHMQ L Ventilation computer with frequency inverter for 1 fans in agriculture Operating Instructions Keep for reference Software version D2512A from Version 02 00 L BAL E139 GB 2022 03 Index 006 P...

Страница 2: ...ning 10 5 Electrical installation 10 5 1 Safety precautions 10 5 2 EMC compatible installation 10 5 2 1 Motor cable 10 5 2 2 Control cables 10 5 3 Mains connection 11 5 3 1 Mains voltage 11 5 3 2 Requ...

Страница 3: ...12 Installation IO Setup 37 7 12 1 Factory setting allocations possible allocations 41 7 13 Installation Diverse 42 7 13 1 Displaymode 42 7 13 2 Switch mode 42 7 13 3 Preheat operation Stall washing...

Страница 4: ...the growth curve 70 9 6 2 Curve for Setpoint compartment temperature 71 9 6 3 Curve for Minimum Ventilation 71 9 6 4 Curve for Maximum Ventilation 72 9 6 5 Curve for Heating1 72 9 6 6 Curve for Heatin...

Страница 5: ...ce between the contents of these operating instructions and the described hardware and software in the device has been examined It is still possible that non compliances exist no guarantee is assumed...

Страница 6: ...nstructions of AEL DLG VdS 2 4 Requirements placed on the personnel due diligence Persons entrusted with the planning installation commissioning and maintenance and servicing in connection with the fr...

Страница 7: ...the device Attention Automatically restart after a power failure or mains disconnection 2 7 Modi cations interventions in the device Attention For reasons of safety no unauthorized interventions or mo...

Страница 8: ...er can be communicated to all system users Fault messages on stall devices are transmitted and displayed as a group fault in addition the total exhaust air volume of the ventilation system is determin...

Страница 9: ...s respectively to the cable diameter Or alternative use cable inlet for cable glands Metal sheet housings are supplied with stoppers Any cable ducts openings not used must be sealed Care must be taken...

Страница 10: ...y For metal cable inlets the necessary protective earth connection to the bottom of the housing is made by screws The device may only be started up when these screws are tted properly The required pro...

Страница 11: ...of a residual current protective device RCD is necessary or allowed depends on the design of the low voltage system on which the device is to be operated The assessment whether or which residual curr...

Страница 12: ...tion modulation remains in operation The control unit with digital and analogue inputs and outputs remains active Possibilities for re starting after the drive has cooled down terminals TB bridged by...

Страница 13: ...hnical data In case of overload or short circuit 24 V GND the external power supply is shut down multi fuse The device performs a Reset and continues operation It is not permissible to connect voltage...

Страница 14: ...ault must be connected at the Master device 5 11 2 RS 485 network design and interface parameter Please ensure the correct connection i e A D must always be connected to A D of the next devices The sa...

Страница 15: ...y Even None exception of devices agriculture Stop bits 1 Handshake none Information If any matters are unclear please contact our V STE support department for control systems ventilation technology Th...

Страница 16: ...d 100 the control unit is switched off and behaves passively stop symbol in display Messages at overtemperature and undertemperature via display and relay K1 are switched off Messages in the case of a...

Страница 17: ...function activ 9 STOP symbol main switch 0 100 10 Bar symbols ventilation modulation corresponds to output A1 11 Text line 3 gures display unit etc 12 KL Opening exhaust air ap F Output frequency Hz...

Страница 18: ...ng1 4 Min ventilation Minimum ventilation Setting Ventilation For Control of Ventilation 5 H2 Setpoint Offset nominal value for heater H2 Settings for heating2 6 Alarm Maximum Setting an absolute temp...

Страница 19: ...adjusted with the keys and then saved with the P key To exit the menu without making any changes use the Esc key i e the originally set values remain One returns to the level menu group Ventila tion...

Страница 20: ...gits etc until PIN 1070 is complete 5 The Installation menu is opened the triangle points to the tool icon Installation 6 Press the P key the rst menu group Ventilation appears in the Installation men...

Страница 21: ...e shutter is fully closed in central exhaust air systems If a Minimal ventilation is set e g 20 the fan is not switched off the shutter is never completely closed in central exhaust air systems i e a...

Страница 22: ...g spring recoil 7 2 3 1 Variant of peak load 1 Control peak load by relay A relay output is available for connecting the peak load fan The setting for peak load on is the point percentage of the contr...

Страница 23: ...mount of air Zuschaltpunkt trigger point variabel 100 100 0 100 0 Ventilator fan 1 nM R 1 Spitzenlast peak load 2 3 4 17 09 2008 v_dia_spila_varia2 vsd 1 Fan 2 Max load 3 Connection point variable 4 P...

Страница 24: ...Ventilation link Ventilation link OFF With the factory setting of OFF the shutter operates completely independent of the fan control I e at the values set for the shutter control offset or setpoint mi...

Страница 25: ...Installation Heating 2 Heating2 ESC P H2 Mode H2 Mode OFF heater inactive at factory 1 Heating works as a two point controller via relay 2 Heating works as a proportional controller 0 10 V 3 piglet n...

Страница 26: ...ased rst e g by 2 3 points This serves to slow down the integration behaviour i e the regulator responds a little slower which normally results in more stability The function and position of the start...

Страница 27: ...etpoint the control range the setpoint is increased via an automatic timer per hour by the adjustable value e g 0 2 K h The increase is only carried out up to a maximal value adjustable via Maximal Ri...

Страница 28: ...on is feasible Setting range 0 100 Factory setting 50 Information Function explanation Ventilation set point derating 7 7 Installation Sensor adjust Sensor adjust ESC P Adjustment E1 Adjustment E1 Sen...

Страница 29: ...or setting the supply air fan Freshair start Setting range 0 100 Factory setting 0 Freshair 100 Setting range 0 100 Factory setting 75 Inlet air maximal Setting range 0 100 Factory setting 100 Inlet a...

Страница 30: ...t is the closing point and Freshairshutter 100 the opening point ON The supply air shutter is controlled linearly by means of the 0 10 V output The shutter between Freshairshutter Start and Freshairsh...

Страница 31: ...lation to stall ventilation Exhaust min Exhaust min Absolute minimum for the group control Setting range 0 100 Factory setting 10 Group version Group version OFF factory setting no group variant 1 two...

Страница 32: ...witch off value for Group5 Setting range 0 100 Factory setting 100 On group5 On group5 Switch on value for Group5 Setting range 0 100 Factory setting 100 Minimum5 Minimum5 Minimum Value for Group5 Set...

Страница 33: ...devices with power unit several fans can be connected in parallel depending on the reference current of the device and the fans motor connection Variant 1 and variant 3 control second group via 0 10...

Страница 34: ...er under Bus Group3 9 M 1 Bus 13 05 2011 v_anschl_group_varia2 vsd M 1 PTE 6 10AHQ X L FTET4 6 10AHMQ L CTE AHX L K3 K3 K3 1 230 V 50 60 Hz 1 230 V 50 60 Hz M 1 M 1 GND GND D D D D GND D D N N N N N N...

Страница 35: ...the heat exchanger into account 7 11 Installation Bus Bus ESC P Address Address Address factory setting Slave mit Address 32 On the master the address is automatically set to 1 display The address fro...

Страница 36: ...A2 A3 Heatex bypass 14 Heat exchanger Bypass 14 Setting range Address OFF 1 31 Factory setting OFF Setting range Function K1 K2 K3 PWM A1 A2 A3 Group1 7 Example Switch on group1 by member Address 3 wi...

Страница 37: ...ir temperature sensor at analog input E2 Bus supply air temperature value is transferred by the master via bus at the factory i e device is a slave E3 fresh air temperature sensor at analogue input E3...

Страница 38: ...ck K3 Antiblock The automatic anti block protection is switched OFF To activate the anti block protection switch to ON The settings for this function are made in the following menu items FSS Interval...

Страница 39: ...S Interval and FSS Runtime A3 output curve A3 output curve Activate characteristic for A3 ON following characteristic points U1 2 function U1 2 function Inverter output U1 U2 factory setting code 0 fo...

Страница 40: ...ching input Off none Function factory setting 1D Fault indication e g von motor protection unit 2D function for D2 prohibited 3D External switch extension Installation 4D function for D2 prohibited 5D...

Страница 41: ...ut 3 0 10 V A3 Heating1 Code 1 Inverter output function U1 U2 Ventilation Code 0 Possibilities for allocation Function Code These functions can be distributed to other devices in a bus system by the m...

Страница 42: ...ypass com pletely open S 20 0 xx _ _ 7 13 2 Switch mode Switch mode Switch mode The factory set switch mode is OFF This means that the control unit is active in all switch positions i e overtemperatur...

Страница 43: ...s active when the device is in the heat mode D1 function 2D and D3 function 3D for operation with external switch switch position 2 setting range 0 0 70 0 C Factorysetting 0 0 20 0 C 7 13 4 External s...

Страница 44: ...ow sensor values per stall are compared constantly and checked for plausibility to increase the operational reliability Sensor diff time Sensor diff time Temperature sensor difference time until fault...

Страница 45: ...of pulses per revolution is entered in the regulator so that all the preconditions for the speed measurement are satis ed The speed is converted into a volume ow based on a reference speed and the co...

Страница 46: ...according to the temperature the shutter opening must be linked additionally to the ventilation regulator The parameter ventilation link enables this by linking the shutter opening to the control of t...

Страница 47: ...measuring fan data Ref air volume reference air ow Setting Volume ow speci cation for the reference speed of the measuring fan Info Depending on the measuring fan type see measuring fan data Ref numb...

Страница 48: ...rrent limit 120 DC brake mode 1 DC brake time 5 sec DC brake level 10 Boost Value 15 0 Suppression1 AUS Range1 min Range1 max Suppression2 AUS Range2 min Range2 max Suppression3 AUS Range3 max Range3...

Страница 49: ...characteristic must take place Generally speaking if the load characteristic is not known as a de nite value the linear characteristic should be set In the case of linear characteristic curves the mo...

Страница 50: ...n In order to prevent overcurrent and unnecessarily high thermal load of the motor do not select to high a setting Adjustment range 0 25 percentage of the maximum output voltage Factory setting 8 VF q...

Страница 51: ...tion is reduced until the set current is set again This prevents overloading of the motor Setting range 100 130 Factory setting 120 E1 Actual Active current limit is signaled by a bright triangle in t...

Страница 52: ...If the application demands safe starting the machine manufacturer or owner must prevent reverse driving rotation by suitable measures With the frequently one behindthe other following DC bracings it c...

Страница 53: ...e type in Hz rpm Suppression1 Factory setting no suppression active OFF Suppression1 Range1 min Setting for Range1 min Setting range Shutdown Freq Range 1 max Range1 min Range1 max Setting for Range1...

Страница 54: ...90 C switch off Temperature ELKO Temperature ELKO Display of DCLink Elco temperature During impermissibly high levels from 75 C on the output power is automatically reduced At 90 C switch off Temperat...

Страница 55: ...is complete Settings for U f characteristic can only be made when no motor modulation is present 2 Set the menu language in the Quick Info menu if necessary To do this press the P key in the overview...

Страница 56: ...Installation access PIN 0000 With active PIN Lock Installation Diverse the release of the settings is cancelled again with PIN 0010 PIN 9090 Restore user setting PIN 9091 To save the basic user settin...

Страница 57: ...f actual value at E3 As long as input in IO Setup not activated display When temperature sensor activated TF in IO Setup D1 Function 6D Display in C if no sensor is connected display 81 6 C Max load M...

Страница 58: ...g range OFF 6 100 Factory setting 20 Minimal ventilation is greater than setting Maximal ventilation Max ventilation Maximum ventilation Setting range 100 50 Factory setting 100 Depending on the softw...

Страница 59: ...or throttle shutter control The shutter function is used to control one throttle shutter in the chimney above or below the fan Shutter offset Shutter offset Setpoint for throttle shutter on 0 10 V out...

Страница 60: ...l set point with active automatic set point derating e g set point 25 0 C plus automatical increasing 0 2 K h The automatic reduction feature automatic setpoint derating is intended to help operate th...

Страница 61: ...control range but these changes would have to be constantly adapted to the corresponding ambient conditions And that is where the automatic reduction function takes over This function relieves you of...

Страница 62: ...humidity maximal Setting range 100 0 Factory setting 100 Information A heater is required in the stall for a perfectly working humidity control Note Due to the in uence of the humidity control the st...

Страница 63: ...0 C setting Alarm Minimum 5 0 K temperature difference in Kelvin Alarm Undertemperature At compartment temperature below 15 0 C Attention Unit in K distance alarm active Alarm Maximum Alarm Maximum If...

Страница 64: ...list Position 0 most recent alarm To exit the alarm menu press the key ESC e g in case of an alarm that was at position 3 Buserror 1 2 Buserror P 00017 16 23 P ED1 2 P ED2 5 ED Event datas 2 controll...

Страница 65: ...et to 60 minutes S 25 C SH 99 5 In the menu group overview Alarm pause appears alternately with the con rmed alarmmessage Alarm Overtemp 6 Past fault messages can be queried in the alarm list Overtemp...

Страница 66: ...SC P Information With the growth program switched on the offset or set value is calculated by the growth program growth program Settings of these functions under Heating are then not possible Display...

Страница 67: ...ive hysteresis value Heating function Relay ON as long as the temperature around the hysteresis is above the switch on point Negative hysteresis value Cooling function Relay OFF if the temperature aro...

Страница 68: ...le for 0 10 V control independent of the ventilation nominal value In Installation menu H1 input 1 for sensor at input E2 2 for BUS from Master or 3 for sensor at input E3 Heating is adjustable as a s...

Страница 69: ...er or 3 for sensor at input E3 Heating is adjustable as a separate setpoint i e in C Setting range 10 0 70 0 C Factory setting 2 0 C H2 Pband H2 Pband Setting range 0 1 10 0 K Factory setting 2 0 K H2...

Страница 70: ...hen superposed by the calculated curve values following diagrams That means the curve values in uence the regulation with an active growth curve Knick point1 Knick point1 Setting Day for break point 1...

Страница 71: ...ing 23 0 C Setpoint nal Setpoint nal setting range 0 0 40 0 C Factory setting 20 0 C 9 6 3 Curve for Minimum Ventilation Minimum curve Minimum curve Factory setting min curve active ON if curve progra...

Страница 72: ...ating 1 H1 input 0 The set offset values refer to the setpoint of the ventilation Heating1 start Heating1 start Setting range 10 0 10 0 K Factory setting 0 0 K Increase program Heating1 Day K 31 10 20...

Страница 73: ...aved with PIN 9091 and restored with PIN 9090 Quickinfo Menu PIN Attention Entering PIN 9095 completely resets the device back into its delivered condition Any changes that have been made to the setti...

Страница 74: ...1 Minimum H1 maximum H2 Setpoint H2 Offset H2 Hysteresis H2 Pband H2 Minimum H2 maximum Day of program Actual day 0 Day Curve program OFF Knick point1 10 Day Knick point2 60 Day Final day 120 Day Setp...

Страница 75: ...and system functions Subsequent modi cations must be coordinated with your electrician We are never liable for damage or harm caused by improper operation or insuf cient knowledge Enter the individua...

Страница 76: ...0 Freshair start 0 Freshair 100 75 Freshair max 100 Inlet air off 70 Offstate temp 18 0 C Off on group 1 Freshairshutter ZK Mode OFF Freshair linear OFF FAS Start 75 ZK 100 90 Changeover temp 10 0 C F...

Страница 77: ...ddress 32 Mastermode 0 MODBUS Slave factory setting 1 MODBUS Master 2 MODBUS passive Master for Alarmcon combination 3 ZABus Slave 4 ZABus Master Mastermode 0 Number slaves Group1 7 Group2 8 Group3 9...

Страница 78: ...F K2 Function 1 K2 Invert OFF K2 Antiblock OFF K3 Function 4 K3 Invert OFF K3 Antiblock OFF A1 Function 0 A1 Invert OFF A1 Antiblock OFF A1 output curve OFF A2 Function 2 A2 Inverting ON A2 Antiblock...

Страница 79: ...ssion2 AUS Range2 min Range2 max Suppression3 AUS Range3 max Range3 max Diagnostic D2 0 Max load OFF Max load K OFF Max load A 0 Controller3 OFF Group OFF Freshairfan 0 Heatex bypass 99 Measuring fan...

Страница 80: ...gged in Check the plug in connections Overtemp Room temperature lies above the set maximum temperature The fault relay K1 responds Check the room temperature Check the set maximum temperature Interrup...

Страница 81: ...approx 10 min The device operates according to temperature message via relay K1 Check of measuring fan and its connection Temperature management active The device has an active temperature manage ment...

Страница 82: ...an 100 11 2 Behaviour of outputs during operation and faults Description of factory settings Output U1 U2 K1 K2 K3 A1 A2 A3 Function 0 Ventilation 3 Fault 1 Heating1 4 Peak load 1 0 Ventilation 2 Shut...

Страница 83: ...FTET6AHMQ L FTET10AHMQ L Part No 308201 308202 308203 Rated current output 1 A 4 6 10 Rated current input 2 A 4 2 6 3 10 8 Max load limit integral of cut in current 2 A2 s 0 6 0 7 1 3 Max leakage curr...

Страница 84: ...with EN 61373 cat egory 1 class B Shock test according to EN 61373 category 1 Housing protection IP54 Regarding the mains connection the Fcontrol devices are to be classi ed as category C2 devices ac...

Страница 85: ...able 15 A D B D MODBUS RS 485 Digital Eingang Input 6 14 1 2 1 Line 1 208 277 V 50 60 Hz 2 1 Motor with internal thermostats 3 Relais K1 pre programmed for Error Alarm 4 Relais K2 pre programmed for H...

Страница 86: ...12 3 Dimensions mm FTET4AHMQ L FTET6 10AHMQ L Operating Instructions Fcontrol model series FTET4 6 10AHMQ L Enclosure L BAL E139 GB 2022 03 Index 006 Part No 86 92...

Страница 87: ...ect all devices 1 3 Line connections and external fault indication not considered Programming of the controllers Device Cot Installation menu Designation factory setting Setting site Information 1 Ven...

Страница 88: ...F Heating two point 21 24 At device for cot 3 Bus Bus connection A D B D GND Connect all devices 1 6 Line connections and external fault indication not considered Programming of the controllers Device...

Страница 89: ...oup 31 32 D3 D3 At device 2 type CTE AH L slave Activation third group Fault indication from motor protection unit S ET10 4 G 1 Asyn ON OFF fourth Group 31 32 D3 D3 At device 3 type CTE AH L slave Act...

Страница 90: ...1 U2 0 7 controlled group 1 for central exhaust air Relays K3 4 8 Switch on group 2 for central exhaus air K3 Antiblock OFF ON Anti block protection for group 2 activated D1 Function OFF 1D or 7D Faul...

Страница 91: ...measuring fan 40 45 Menu language 57 minimum air ventilation 21 Minimum space requirement 9 Minimum speed cut off 21 mixer valve 26 MODBUS 14 motor feed cable 10 motor leads 11 motor protection unit 1...

Страница 92: ...de http www ziehl abegg com 12 7 Service note If you have any technical questions while commissioning or regarding malfunctions please contact our technical support for control systems ventilation tec...