K2 Invert.
K2 Invert.
Inversion of the relay function with pre-programmed function code
|
1
|
for heater:
|
OFF
|
= (factory setting) relay
“
K2
”
attracts so that the heating is active (i.e. terminals
21 - 24 bridged).
|
ON
|
= Relay
“
K2
”
releases so that the heating is active (i.e., terminals 21 - 22 are
bridged).
K2 Antiblock
K2 Antiblock
The automatic anti block protection is switched =
|
OFF
|
.
To activate the anti block protection, switch to
|
ON
|
.
The settings for this function are made in the following menu items
“
FSS Interval
”
and
“
FSS Runtime
”
.
K3 Function
K3 Function
Relay
“
K3
”
, factory setting Code
|
4
|
for peak load.
Other functions which can be assigned
Factory assignments / possible assign-
ments.
K3 Invert.
K3 Invert.
Inversion of the relay function with pre-programmed function code
|
4
|
for Peak load:
|
OFF
|
= (factory setting) relay
“
K3
”
energizes in operation without peak load fan and
de-energizes when the peak load fan is activated (i.e. terminals 31 - 32 bridged).
|
ON
|
= (factory setting) relay
“
K3
”
de-energizes in operation without peak load fan and
energizes when the peak load fan is activated (i.e. terminals 31 - 34 bridged).
K3 Antiblock
K3 Antiblock
The automatic anti block protection is switched =
|
OFF
|
.
To activate the anti block protection, switch to =
|
ON
|
.
The settings for this function are made in the following menu items
“
FSS Interval
”
and
“
FSS Runtime
”
.
A1 Function
A1 Function
Analog output
A1
factory setting code
|
0
|
for ventilation.
Other functions which can be assigned
Factory assignments / possible assign-
ments.
A1 Inverting
A1 Inverting
|
OFF
|
= 0...10 V (
factory setting
)
|
ON
|
= 10...0 V
Attention: When using output characteristic curve operation without inverting!
A1 Antiblock
A1 Antiblock
The automatic anti block protection is switched
|
OFF
|
.
To activate the anti block protection, switch to
|
ON
|
.
The settings for this function are made in the following menu items
“
FSS Interval
”
and
“
FSS Runtime
”
.
A1 output curve
A1 output curve
Activate characteristic for A1 =
|
ON
|
(
following characteristic points)
A2 Function
A2 Function
Analog output
A2
factory setting Code
|
2
|
for throttle shutter.
Other functions which can be assigned
Factory assignments / possible assign-
ments.
A2 Inverting
A2 Inverting
|
OFF
|
= 0...10 V
|
ON
|
= 10...0 V (
factory setting
)
Attention: When using output characteristic curve operation without inverting!
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ-L
The Installation menu
L-BAL-E139-GB 2022/03 Index 006
Part.-No.
38/92