D1 Function
D1 Function
D1 function determines the function of the digital switching input
|
Off
|
= none Function (
factory setting
)
|
1D
|
= Fault indication e.g. von motor protection unit
|
2D
|
= External switch extension (
Installation)
|
3D
|
= function for D1 prohibited
|
4D
|
= operation with measuring fan (the additional menu group appears in the
Installation menu after
“
Diverse
”
)
|
5D
|
= function for D1 prohibited
|
6D
|
= function for D1 prohibited
|
7D
|
= fault message
“
ALARM fan
”
also for
“
stall OFF
”
D2 Function
D2 Function
D2 function determines the function of the digital switching input
|
Off
|
= none Function (
factory setting
)
|
1D
|
= Fault indication e.g. von motor protection unit
|
2D
|
= function for D2 prohibited!
|
3D
|
= External switch extension (
Installation)
|
4D
|
= function for D2 prohibited
|
5D
|
= function for D2 prohibited
|
6D
|
= function for D2 prohibited
|
7D
|
= fault message
“
ALARM fan
”
also for
“
stall OFF
”
Antiblock interv.
Antiblock interv.
Jammin gof other groups or peak load fans which are controlled by relays or 0 - 10 V
signal can be prevented by connecting these fans for a certain time at an adjustable
interval.
These settings act together on all outputs with activated anti block function.
Setting range: 1...250 days
Factory setting: 1 day
Antiblock runtime
Antiblock runtime
Setting range: 5...250 sec.
Factory setting: 60 sec
Example for factory setting: The activated output switches on for 60 seconds every
day.