9.4
Setting temperature monitoring
Alarm
Alarm
Whether or not a malfunction is present is shown for informational purposes
•
OFF = currently no alarm pending
•
ON = Alarm is pending
The pending alarm message is displayed alternating e.g. during over temperature.
↑
|
ESC
|
P
↓
Alarm
Overtemp.
Alarm Minimum
Alarm Minimum
If the compartment temperature sinks below this value, a low temperature alarm is
triggered (approx. 60 sec. time delay). The relay
“
K1
”
switches. Message:
“
Under temper-
ature
”
and entry in the alarm list.
•
Setting an absolute temperature minimum (at factory)
–
Setting range: 0.0...35.0
°
C
–
Factory setting: 10.0
°
C
Alarm Minimum
•
Setting a relative temperature minimum (alternative)
–
Setting range: -40.0...5.0 K
–
Factory setting: -5.0 K
Function can be activated in the Installation menu
/ Various / Temperature monitoring
by distance alarms.
Example:
Active nominal value = 20.0
°
C, setting
“
Alarm Minimum
”
= -5.0 K (temperature difference
in Kelvin)
Alarm
“
Undertemperature
”
: At compartment temperature below 15.0
°
C
Attention!
Unit in
|
K
|
= distance
alarm active!
Alarm Maximum
Alarm Maximum
If the compartment temperature rises above this value, an excess temperature alarm is
triggered (approx. 60 sec. time delay). The relay
“
K1
”
switches. Message:
“
Over temper-
ature
”
and entry in the alarm list.
•
Setting
an absolute temperature maximum
(at factory)
–
Setting range: 10.0...40.0
°
C
–
Factory setting: 35.0
°
C
Alarm Maximum
•
Setting a
relative temperature maximum
(alternative)
–
Setting range: -5.0...40.0 K
–
Factory setting: +5.0 K
Function can be activated in the Installation menu
/ Various / Temperature monitoring
by distance alarms.
Example:
Active nominal value = 20.0
°
C, setting
“
Alarm Maximum
”
= 5.0 K (temperature difference
in Kelvin)
Alarm
“
Undertemperature
”
: At compartment temperature over 25.0
°
C
Attention!
Unit in
|
K
|
= distance
alarm active!
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ-L
Settings for operation
L-BAL-E139-GB 2022/03 Index 006
Part.-No.
63/92