9.6.2.10
Switch over Setpoint 1/2 for control circuit 2
|
9D
|
Switch over between
“
2.Setpoint 1
”
and
“
2.Setpoint 2
”
(for operation with two control circuits)
Contact at digital input e.g.
“
Digital In 1
”
(terminals
“
D1
”
-
“
D1
”
).
Controller
1
0
n = 0 – 100 %
- - - - -
- - - - -
Sensor
27.11.2008
v_5d_sollwert_1_2_m.vsd
1
2
D1 D1
M
1
Setting
“
Setpoint 1
”
or
“
1.Setpoint 1
”
(display in operation with two
control circuits for Setpoint 1 of control circuit 1)
2
Setting
“
Setpoint 2
”
or
“
1.Setpoint 2
”
(display in operation with two
control circuits for Setpoint 2 of control circuit 1)
•
“
D1 Inverting
”
=
“
OFF
”
:
“
2. Setpoint 1
”
=
18
°
C at opened contact /
“
2. Setpoint 2
”
=
25
°
C at closed contact.
•
“
D1 Inverting
”
=
“
ON
”
:
“
2. Setpoint 1
”
=
18
°
C at closed contact /
“
2. Setpoint 2
”
=
25
°
C at opened contact.
Info
Operation with
“
1.Setpoint2
”
is signalized by the moon symbol for reduced operation.
If Setpoint 2 was activated additionally for control circuit 1
“
1.Setpoint 2
”
by a digital
input with function
|
5D
|
, the moon symbol is already switched on.
28.7
°
C
E2 Actual
9.6.2.11
Reset, Function
|
10D
|
Reset after motor fault by using an non-locking reset key. The unit switches off when interruption
between both
“
TB/TP
”
or
“
TK/PTC
”
terminals, the unit then remains switched off (
“
motor fault
”
see
motor protection). Re-starting after the drive has cooled down (terminals
“
TB/TP
”
- or
“
TK/PTC
”
bridged) by non-locking reset key possible.
M
27.11.2008
v_10d_reset_m.vsd
Controller
D1 D1
Reset
TB/TP
Contact at digital input e.g.
“
Digital In 1
”
•
For
“
D1 Inverting
”
=
“
OFF
”
both terminals
“
D1
”
-
“
D1
”
in normal operation interrupted.
Reset after fault by short close.(For
“
Invert-
ing
”
=
“
ON
”
reverse function).
Operating Instructions
Fcontrol
–
model series FKDM25/32AM-C
Programming
L-BAL-E214-GB 1446 Index 002
Part.-No.
53/99