
9.8
Motor Setup
Main menu
Motor Setup
Controller Setup
IO Setup
Limits
Motor Setup
Diagnostic
9.8.1
Setting motor rated current
Motor Setup
MotorRatedCurr.
Possible setting for the motor rated current.
The setting for the
“
DC brake level
”
(
setting brake behaviour) refers to this setting.
Setting range: 0.0...device rated current / A
Factory setting: device rated current
32 A
MotorRatedCurr.
9.8.2
Setting motor rated voltage
Motor Setup
MotorRatedVolt.
When commissioning, you must set the motor to the rated voltage stated on the
rating plate.
An adaptation can be made if the motor rated-voltage as the applied mains voltage is
lower (e.g. 3 ~ 230 V motor on 3 ~ 400 V mains).
Verify the output voltage using suitable measuring instruments.
Setting range: 0...500 V
Factory setting: 400 V
400 V
MotorRatedVolt.
9.8.3
Adjustment of the U/f curve
Information
Settings for U/f characteristic may only be made when no motor modulation is present!
Motor Setup
Edgefrequency
The maximum output voltage is attained during break edge frequency.
Adjustment range: 10.0 - 150.0 Hz
Factory setting:
1.10
,
3.10
,
3.20
= 48.5 Hz
1.11
,
3.11
,
3.21
= 85.0 Hz
48.5 Hz
Edgefrequency
Motor Setup
Max. Frequency
Above the Edgefrequency, the frequency is merely increased up to the Maximum
frequency.
Adjustment range: 10.0 - 150 Hz
Factory setting:
1.10
,
3.10
,
3.20
= 50.0 Hz
1.11
,
3.11
,
3.21
= 87.0 Hz
50.0 Hz
Max. Frequency
Motor Setup
Shutdown Freq.
Below the Shutdown Freq. the output is switched off (hysteresis approx. 1.5 % setting
“
Max. Frequency
”
) .
Adjustment range: 5.0 - 150 Hz
Factory setting: 5.0 Hz
5.0 Hz
Shutdown Freq.
Operating Instructions
Fcontrol
–
model series FKDM25/32AM-C
Programming
L-BAL-E214-GB 1446 Index 002
Part.-No.
68/99