7.3
External Setpoint / External speed setting in manual operation
External Setpoint or external manual operation is possible by 0 - 10 V (0 - 20 mA, 4 - 20 mA) signal at terminals
“
E2
”
and
“
GND
”
.
“
E2
”
con
fi
guration in base setup. For Potentiometer Analog Out1 (terminal
“
A1
”
) program to function
|
1A
|
=
“
+10 V
”
(like factory
setting
IO Setup). If a second sensor is connected at input 2 external Setpoint or speed setting in manual operation is
possible with additional modul
“
Z-Modul-B
”
(input E3
IO Setup / programming additional modul type Z-Modul-B).
E2 Analog In = factory setting 0 - 10 V
23.09.2011
v_extern_pot.vsd
0 - 10 V
0 - 10 V
10 k
A1
GND
E2
GND
External Setpoint
via external signal instead of
“
Setpoint 1
”
. The
“
external Setpoint
”
function must be activated in base setup
|
1E
|
for
“
E3 function
”
. The active external Setpoint value is displayed in the
“
info
”
menu group.
External speed setting
in manual operation. The
“
external manual operation
”
function must be activated in the basic settings
|
2E
|
for
“
E3 function
”
. Switchover between settings on the device and external manual operation via the digital input (
IO
Setup:
“
Control / manual operation
”
|
7D
|
).
8
Start-up
8.1
Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the hazardous area.
Operating Instructions
Fcontrol
–
model series FKDM25/32AM-C
Start-up
L-BAL-E214-GB 1446 Index 002