9.12 Motor Setup
9.12.1
Menu
“
Motorsetup
”
Motor Setup
Menu group Motorsetup
Parameter
Factory setting
User Setting
Rated Speed
200 rpm
Polecount
4
Rolling direct.
1
MotorRatedCurr.
6.0 A
Econtrol > 10A
OFF
PI Mode
1
Rampup time
20 sec
Rampdown time
20 sec
Derating Alarm
5 %
Suppression1
OFF
Range1 min.
- - - -
Range1 max.
- - - -
Suppression2
OFF
Range2 min.
- - - -
Range2 max.
- - - -
Suppression3
OFF
Range3 min.
- - - -
Range3 max.
- - - -
9.12.2
Setting motor rated speed
Attention!
Maximum speed limiting , important setting!
For EC-Motors a limiting to the maximum permissible speed is required under all circumstances (refer
to the rated speed given on the fan
´
s nameplate).
Overloading can occur if the speed is not limited, an this can lead to damage to the motor or to the EC-
Controller!
Rated Speed
Rated Speed
Setting range: 0...6000 rpm
Factory setting: 200 rpm
For reasons of safety, the maximum speed is preprogrammed in the
factory to only 200 rpm!
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
68/85