E3* Function
OFF
|
14D
|
“
Freeze
”
function modulation value
E3* Inverting
- - - -
E3 Function
K1 Function
1K (2K**)
|
1E
|
0 - 10 V external Setpoint
K1 Inverting
OFF
|
2E
|
External Manual mode
K2 Function
2K (9K**)
K1...K4function
K2 Inverting
OFF
|
1K
|
Operating indication
K3* Function
OFF
|
2K
|
Fault indication
K3* Inverting
- - - -
|
3K
|
External alarm indication
K4* Function
OFF
|
4K
|
Limit modulation
K4* Inverting
- - - -
|
5K
|
Limit E1
Bus Address
247
|
6K
|
Limit E2
Addressing
OFF
|
7K
|
Setpoint Offset
* IO option Add-on module type Z-Modul-B
|
8K
|
Group control
** Deviating factory setting for mode
2.03
|
9K
|
only 2.03 Heating function
|
- - - -
|
= display as long as no allocation has been carried
out
|
10K
|
only 2.03 Cooling function
9.10.2
Analog-Output
“
A
”
AFunction
The analog outputs 0 - 10 V can be allocated with various functions.
Terminals
“
A
”
-
“
GND
”
= Analog Out (I
max
10 mA)
Amin.
With the attitudes
“
A min
”
and
“
A max
”
the characteristic of the output voltage
can be adapted.
Setting range:
“
A min.
”
= 0 - 5 V,
“
A max.
”
= 10 - 5 V
Factory setting:
“
A min.
”
= 0 V,
“
A max.
”
= 10 V
Amax.
AInverting
With the attitudes
“
A Inverting
”
the output voltage can inverted.
Factory setting:
“
A Inverting
”
=
“
OFF
”
Function
Description
OFF
without function
1A
Constant v10 V (factory setting)
2A
Proportional the internal control of modulation with consideration
“
Min. speed
”
and
“
Max. speed
”
setting.
•
for enable
“
OFF
”
it goes back to 0 V
•
for motor fault the output signal remains for a slave controller (
“
Master-Slave
”
combination).
3A
proportional input
“
E1
”
4A
proportional input
“
E2
”
5A
Group control (
F
Controller Setup - second group)
6A
Control output 2 increasing modulation at actual value > Set = cooling (only mode
2.03
temperature controller with additional functions).
7A
Control output 2 incresing modulation at actual value < Set (Heating) only mode
2.03
temperature controller with additional functions).
9A
Output speed
ratio: actual speed / rated speed (for 10 V actual speed = rated speed)
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
53/85