9.4Pressure control airconditioning
4.01
...
4.03
9.4.1
Base setup
4.01
...
4.03
Base setup
Base setup
Mode
Mode
Mode selection e.g.
4.01
E1 Analog In
E1 Analog In
In all group 2 operating modes 4 (
4.01
,
4.02
,
4.03
, ....)
“
E1 Analog In
”
factory
setting
“
DSG200
”
.
Selection sensor measuring range:
“
DSG50
”
,
“
DSG100*
”
,
“
DSG200
”
,
“
DSG300
”
*,
“
DSG500
”
,
“
DSG1000
”
,
“
DSG2000
”
,
“
DSG4000
”
,
“
DSG6000
”
(* no standard type).
For sensors with 0 - 20 mA or 4 - 20 mA signal (
F
jumper for input signal),
select measuring range
“
DSG50
”
...
“
DSG6000
”
.
For not preprogrammed measuring range the sensor measurement range
must be entered in order to display the actual value correctly.
Example with a 0 - 10 V sensor and 0 - 400 Pa measurement range (propor-
tional output signal):
E1 Analog In = 0 - 10 V, E1 Min. = 0.0 Pa, E1 Max. = 400 Pa, E1 Dezimal = 1,
E1 Einheit = Pa
E1 Offset
E1 Offset
Sensor calibration with calibrated comparison device