Speed man.
Speed manual
Manual speed setting without in
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
F
IO
Setup).
Setting range: 0...100 %
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual
speed is indicated alternating with the actual value.
9.3.3
Functional diagrams pressure control condensers
Functional diagram for Mode
3.01
and
3.03
(Idealized principle diagram)
nM
50 %
100 %
I
Min.
Min. 0 %
Max. = 100 %
12 bar
S
5 bar
R
17 bar
09.05.2007
v_diagramm_301_303_bar.vsd
nM Motor speed
S Setpoint
R Pband
I Actual value
Functional diagram for Mode
3.02
and
3.04
(Idealized principle diagram)
nM
50 %
100 %
I
Min. 0 %
Max. = 100 %
35 °C
S
7 K
R
42 °C
09.05.2007
v_diagramm_302_304_c.vsd
nM Motor speed
S Setpoint
R Pband
I Actual value
Information
The factory default presets must be adapted to match the system conditions by a competent
person.