![ZIEHL-ABEGG Econtrol EXDM Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/ziehl-abegg/econtrol-exdm/econtrol-exdm_operating-instruction_933534038.webp)
E2 Function
E2 Function
(only for special applications)
•
External setpoint = Function
|
1E
|
by external signal (0 - 10 V) instead of
“
Setpoint1
”
. 0 - 10 V
≙
0 - 100 % sensor measuring range.
•
External manual operation via external signal (0 - 10 V) = Function
|
2E
|
Switch over between settings on the device and external manual
operation via digital input (
F
IO Setup).
•
Measurement value = function
|
7E
|
e.g. for limit indication, display in Info
menu
“
E2 Actual.
”
Modes
4.02
and
4.03
with two sensors
The function is automatically jointly programmed in operating modes using 2
sensors. The second analog input is thus allocated and additional function
allocations are not possible.
For
4.02
E2 Function at
|
6E
|
preprogrammed = sensor for setpoint lowering.
Preprogrammed sensor type
“
TF..
”
For
4.03
|
E2
|
Function at
|
6E
|
preprogrammed = sensor for setpoint low-
ering.
- preprogrammed sensor type
“
BUS
”
- measuring range -35.0...+65.0
°
C
In
“
IO Setup
”
:
For enable
“
ON
”
/
“
OFF
”
via Bus:
- D1 function =
|
1D
|
- D1 Busmode =
“
ON
”
For switch over setpoint 1 /2 via Bus:
- D2 function =
|
5D
|
,
- D2 Busmode =
“
ON
”
9.4.2
Setting for operation modes
4.01
...
4.03
•
4.01
pressure control, setpoint in Pa
•
4.02
and
4.03
Pressure control for ventilation systems setpoint depending on outdoor temper-
ature
Setting
Setting
Setpoint1
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 100 Pa
Setpoint2
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried
out: Display:
|
- - - - -
|
F
IO Setup).
Pband
Pband
small control range = short control times
big control range = longer control times and (higher controller stability)
Setting range: in measuring range of sensor
Factory setting: 100 Pa
Min. Speed
Minimal Speed
Setting range: 0...100 %
Factory setting: 0 %
Max. Speed
Maximal Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
37/85