Watchdog Mode
Watchdog Mode:
0: No function (default) = OFF from FW 13
1: Fault (K1 function, h15) in case of communication fault (WDT)
2: Constant speed 1 * in case of communication fault (WDT)
3: Fault + constant speed 1 * in case of communication fault (WDT)
4: Fault by E1 Fault ** (only ECblue)
5: Constant speed 1 by E1 Fault (only ECblue)
6: Fault constant speed 1 in case of E1 fault (only ECblue)
* in this condition it is possible by digital input function 5, 6 or digital control function to
change between the constant speeds (Holding register h4).
** E1 fault is triggered when E1 falls below E1 min x 0.5. E1 fault is cancelled when E1
rises above E1 min x 0.9.
8.6.5
Networking via MODBUS
It is possible to network several devices with each other. The device uses the MODBUS-RTU as the
protocol for the RS-485 interface.
Bus Address
The device address is factory set to the highest available MODBUS address: 247.
Setting range MODBUS Address: 1 - 247.
UART Baudrate
Setting transfer rate
Valid values: 4800, 9600, 19200, 38400
Factory setting: 19200
Illegal value: 115200
UART Mode
Setting transfer format
Valid values: 8O1, 8N1, 8E1
Factory setting: 8E1
Information
If it is attempted to change the baud rate to an impermissible value (e.g. 115200), the following
exception code will be sent back:
|
Exception Code 3: Illegal Data Value
|
.
8.7
Menu group
“
Motor Setup
”
Motor Setup
Rated speed
Motor rated current
*The following controller presets are dependent on the re-
spective motor design.
These are shown for informational purposes and must only
be changed after consultation with ZIEHL-ABEGG and enter-
ing a password.
•
Rated speed
•
Motor rated current
•
Rotat. Direction
•
Value motorheating
Rampup time
Assembly instructions
ECblue
Programming by hand held terminal A-G-247NW
L-BAL-F055D-GB 1634 Index 002
Part.-No.
35/51