8.5.4
PIN-Accesslevel
PIN-Accesslevel
The PIN-Accesslevel determines for which setting ranges a PIN must be entered.
Setting
Function
2
Factory setting
All menu groups are visible, settings are possible without a PIN.
1
•
The menu group
“
Setting
”
is free, i.e. changes are possible without a PIN.
•
PIN 0010
: for changes in the menu groups:
“
Controller Setup
”
,
“
IO Setup
”
and
“
Motor Setup
”
(these menu groups are not visible without a PIN).
0
All settings are only possible after entering a PIN.
•
PIN 1234
for changes in the menu group:
“
Setting
”
•
PIN 0010
: for changes in the menu groups:
“
Controller Setup
”
,
“
IO Setup
”
and
“
Motor Setup
”
(these menu groups are not visible without a PIN).
Information
Changes for the PIN protection which effect a reduced access right only become active after switching
off the device or executing the
“
Reset
”
(
Start menu group) function.
8.5.5
Tacho output f
out
Tacho out
See the function description Electrical installation / Open-Collector output
“
A1
”
Setting
Function
OFF
A1 = Status output
ON
A1 = Tacho output (n = f x 60)
8.5.6
Message at speed deviation
“
Fan Bad
”
Fanbad Speed
Speed deviation
Factory setting: 0 rpm
Setting range: 0 - 255 rpm
Fanbad Time
Time delay
Factory setting: 0 sec
Setting range: 0 - 255 sec.
8.6
Menu group IO Setup
IO Setup
Information
The following factory settings speci
fi
cations are not binding, these values can differ depending on the
software version and customer-speci
fi
c pre-setting.
Assembly instructions
ECblue
Programming by hand held terminal A-G-247NW
L-BAL-F055D-GB 1634 Index 002