![ZIEHL-ABEGG ECblue Series Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/ziehl-abegg/ecblue-series/ecblue-series_assembly-instructions-manual_933568016.webp)
5.3
Version without connection cables
29.08.2013
v_anchluss_ecblue_B.vsd
1
2
4
5
6
3
1
Cover for terminal compartment
2
Cable glands (2 x M16)
seal insert with two holes 5 mm for two cables applicable if necessary
3
Do not loosen the safety screws from the housing!
4
Connection control system
5
Connection alarm relay and mains connection
6
Status LED
Procedure:
1. Remove the cover from the terminal compartment for the connection.
2. Both cable entry points are in a sealed condition at delivery.
–
Turn in cable gland until seal breaks.
–
Unused entry points must be sealed!
3. When using the seal insert for two cables it is not permissible to use the corresponding cable
gland with only one cable.
4. Insert and connect cables properly and ensure tightness of the cable glands.
5. Attach connection cover again carefully in correct position before start-up.
Attention!
•
Temperatures up to 80
°
C can be present on the controller housing.
•
To connect, always use heat resistant wires or, as an alternative, silicon tubes.
•
Only use lines which can guarantee a permanent seal around the cable glands (pressure-resistant,
dimensionally-stable, round-centred jacket; e.g. by means of gusset
fi
lling)! Lines with
fi
lling
fl
eece
are not permissible because moisture can penetrate due to the capillary effect!
•
Make absolutely sure that different connections do not come into contact (e.g. by splaying or loose
connecting wires).
•
Remants from installation and foreign object may not remain on the inside!
Assembly instructions
ECblue
Electrical installation
L-BAL-F055D-GB 1634 Index 002
Part.-No.
16/51