Function Status Controller
K1
1 = energized
0 = de-energized
Inverting
OFF
ON
1K
Operation without fault, line supply okay
1
0
2K
Fault with indication by relay
0
1
4K
Exceed Frequency / Speed > setting
“
Set Internal3
”
1
0
20K
Fault indication or message for active temperature management
0
1
8.6.3
Input
“
E1
”
E1 Function
|
1E
|
(factory setting) = speed setting by external signal (0 - 10 V / PWM).
For settings via
|
1E
|
“
E1
”
operates like
“
D1
”
as a digital input (
Digital inputs /
function).
E1 Inverting
Factory setting inverting to
“
OFF
”
.
For control with inverted setting signal switch to
“
ON
”
(setting signal: 10 - 0 V).
E1 min.
Value of the input signal at which the controller starts at minimum modulation.
Setting range: 0 - 100 %
Factory setting: 5 %
E1 max
Value of the input signal at which the maximum modulation of the controller is reached.
Setting range: 0 - 100 %
Factory setting: 100 %
Assembly instructions
ECblue
Programming by hand held terminal A-G-247NW
L-BAL-F055D-GB 1634 Index 002
Part.-No.
33/51