![ZIEHL-ABEGG DControl PKDM Series Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/ziehl-abegg/dcontrol-pkdm-series/dcontrol-pkdm-series_operating-instructions-manual_933532005.webp)
Operating instructions
Dcontrol
Date 0730
TBL02_54-GB 0730
Part-No. 00153238-GB
Page 5 / 28
3. General description
3.1 Scope of applications
The controlling device as described is intended for infinitely variable speed settings in voltage-regulated 3-phase motors
for driving fans and pumps.
3.2 Technical data
The name plate data refer to a maximum ambient temperature of 40°C. (with internal semiconductor fuses) or 50°C
(without internal semiconductor fuses).
Type
Part.-
No.
Rated current for
40°C {1}
[A]
max. line fuse {2}
[A]
internal semiconductor fuse
{3}
(Part-No.)
Heat dissipation
approx. [W]
Weight
[kg]
Line voltage
PKDT5
304555
5
2.4
PKDT5*
304556
5
2.4
PKDM5
304558
5
2.4
PKDM10
304559
10
50
2.8
PKDM12
304570
12
55
3.4
PKDM15
304560
15
20
70
4.7
PKDM20
305594
20
25
FF30A 10x38mm gRL
single fuse 00155984
80
5.7
PKDM25
305532
25
35
FF50A D02
pack of 10 fuses: 349028
100
12.7
PKDM35
305533
35
50
FF63A D02
pack of 10 fuses: 349029
150
13.0
PKDM50
305563
50
63
FF100A NH00
single fuse 00150230
170
19.5
PKDM80
305564
80
100
FF160 A NH00
single fuse (00089793)
270
20.5
PKDM20(500V)
305600
20
25
FF30A 10x38mm gRL
single fuse 00155984
80
5.7
3~ 208 - 500 V, (-10 % .. +10%)
50/60 Hz
Type
Part.-
No.
Rated current for
50°C {1}
[A]
max. line fuse {2}
[A]
semiconductor fuse
installation on site {4}
(Part.-No)
Heat dissipation
approx. [W]
Weight
[kg]
Line voltage
PKDT5Z
304573
5
10
25
2.4
3~ 415 V, (-18 % .. +6 %)
50/60 Hz
PKDM10Z
304574
10
16
45
2.8
PKDM12Z
304575
12
16
50
3.35
PKDM15Z
304576
15
20
65
4.7
PKDM20Z
305597
20
25
FF30A 10x38mm gRL
single fuse 00155984
75
5.65
PKDM25Z
305576
25
35
FF 50 A D02
(fuse kits 349030)
95
12.2
PKDM35Z
305577
35
50
FF 63 A D02
(fuse kits 349031)
140
13.0
PKDM50Z
305578
50
63
FF100 A NH00
(fuse kits 349032)
160
19.5
PKDM80Z
305579
80
100
FF160 A NH00
(fuse kits 349033)
255
20.5
Type
Part.-
No.
Rated current for
50°C {1}
[A]
max. line fuse {2}
[A]
semiconductor fuse
installation on site {4}
(Part.-No)
Heat dissipation
approx. [W]
Weight
[kg]
Line voltage
PKDM25E
305547
25
35
FF 50 A D02
(fuse kits 349030)
95
7.2
PKDM35E
305548
35
50
FF 63 A D02
(fuse kits 349031)
140
7.4
PKDM50E
305588
50
63
FF100 A NH00
(fuse kits 349032)
160
13.8
PKDM80E
305589
80
100
FF160 A NH00
(fuse kits 349033)
255
15.4
version: housing IP54, no internal semiconductor fuses
version: housing IP54, internal semiconductorfuses
version: housing IP20 for switch cabinet mounting, no internal semiconductor fuses.
FF30A 10x38mm
pack of 10 fuses: 349027
FF20A 6x32mm
pack of 10 fuses : 349026
3~ 208 - 415 V, (-10 % bis +6 %)
50/60 Hz
3~ 208 - 415 V, (-10 % bis +6 %)
50/60 Hz
10
25
16
3~ 415 V, (-18 % .. +6 %)
50/60 Hz
3~ 208 - 415 V, (-10 % bis +6 %)
50/60 Hz
FF30A 10x38mm
pack of 10 fuses: 349027
FF20A 6x32mm
Pack of 10 fuses : 349026
* for “mobile application“ version, phase failure is deactivated!
{1} for line voltage 400 V / 50 Hz or 500 V / 50Hz for special version PKDM..(500V)
{2} Max. supply side line fuse according to DIN EN 60204-1 classification VDE0113 chapter 1
{3} with internal semiconductor fuse (no line protection)
{4} semiconductor fuse installation on site recommended. Protection for damages in the case of short-circuits. Not in the scope of suply, as accessories available!